Mammoth V-Cube Slim Split IOM, MAMM-VCS-IOM-3FA (September 2013) 5
Disassembly and Assembly
General Guidelines
The Mammoth V Cube Slim Split is engineered to be
disassembled in the field and moved through 36” doors
into position then reassembled without breaking into the
refrigeration circuits. Only qualified personel experienced
in operation and maintenance of HVAC equipment should
perform these procedures.
WARNING! This equipment presents hazards
of electricity, rotating parts, sharp edges,
heat and weight. Failure to read and follow
these instructions can result in property dam-
age, severe personal injury or death. This
equipment must be installed by experienced,
trained personnel only.
WARNING! A mechanical lift is required to
move or lift all sections of a V-Cube Slim™
unit. Do not attempt to move or lift sections
without a mechanical lift. Failure to do so can
result in equipment damage, severe personal
injury or death.
WARNING! Lifting the entire unit (blower
section, coil section, etc.) using lifting lugs,
eye bolts or straps attached to the top of the
unit can result in serious damage to the unit,
personal injury or death.Lifting the entire unit
should only be done using a forklift or a strap-
ping spreader bar mechanism attached to the
base of the unit.
WARNING! All utilities (water, electric, and
communication cables) must be removed
prior to unit disassembly. Follow approved
lockout/tagout procedures before any disas-
sembly of the unit. Failure to do so can result
in electric shock, equipment damage, severe
personal injury, or death.
IMPORTANT! All blower wiring is correctly
phased at the factory and must be re-wired
correctly upon re-assembly for correct com-
pressor and blower operation. Mark all wires
and pull through knockouts using care not
to scrape the insulation of the wiring when
separating sections. If the wire insulation or
wire jacket is torn during the disassembly/
re-assembly procedure, replace the wire. Do
not use wire that is missing insulation. Con-
trol and sensor wiring uses Molex plugs for
proper polarity.
Figure 1 shows the unit as shipped from the factory. Fig-
ure 2 shows an exploded view of the unit, equipped with
coil cabinets and 2” x 4 “ filter racks. Note that the coil
cabinets and refrigeration sections are resting on welded
steel bases. These bases are an integral part of the sub-
assemblies and must not be removed.
IMPORTANT! The welded steel bases are
integral to subassembly stability and mobility.
Do not detach!
Figure 1: Unit As Shipped
Welded steel base