Mammoth V-Cube Slim Split IOM, MAMM-VCS-IOM-3FA (September 2013) 20
Table 5: Square D Molded Case Circuit Breakers – Mechanical lug kit wire ranges and torques
Lug Kit
Lugs
Per Kit
Circuit
Breaker
Wires Per Lug and Wire Ranges
Lug Mounting
Screw Torque
Wire Binding Screw Torque
Wires
Domestic
Metric
Lb-in.
N•m
Wire*
Lb-in.
N•m
AL50FA
3
FA, FH, FI
1
#14–#4 Cu or
#12–#4 Al
2.5–25 mm
2
4–25 mm
2
40
4.5
Cu #14–#4 STR/
SOL
Al #12–#4 STR
Al #12–#10 SOL
35
35
15
4.0
4.0
1.7
AL100FA4
3
FC
1
#14–#3 Cu or
#12–#1 Al
65
7.3
Cu #14–#3 STR
Cu #14–#8 SOL
Al #8–#1 STR
Al #12–#10 SOL
65
65
65
65
7.3
7.3
7.3
7.3
AL100FA
3
FA, FH, FI
1
#14–1/0 Cu or
#12–1/0 Al
2.5–50 mm
2
4–50 mm
2
40
4.5
Cu #14–1/0 STR
Al #12–1/0 STR
Al #12–#10 SOL
80
80
40
9.0
9.0
4.5
AL100TF
3
FA, FH
1
#12–#3 Cu
50
5.7
Cu #12–#3 STR
Cu #12–#10 SOL
50
50
5.6
5.6
AL250KA
3
KA, KH, KC, KI
1
#6–#350 kcmil
25–185 mm
2
80
9.0
250
28.2
AL250KI
3
KC, KI
1
1/0–#350 kcmil
50–185 mm
2
80
9.0
250
28.2
AL400LA
1
Q4, LA, LH
1
2
#0–#600 kcmil or
#1–#250 kcmil»
50–300 mm
2
50–120 mm
2
180
20.0
300
33.9
AL800MA7
1
MA, MH
2
#500–#750 kcmil
240–300
mm
2
180
20.0
300
33.9
AL900MA
1
MA, MH
3
3/0–#500 kcmil
95–240 mm
2
180
20.0
300
33.9
AL1000MA
1
MA, MH
4
1/0–#350 kcmil
50–185 mm
2
180
20.0
300
33.9
AL1200NE6
1
NA, NC
4
3/0–#600 kcmil
95–300 mm
2
250
28.2
330
37.3
AL2500PA
2
PAF, PHF, PCF
1
3/0–#750 kcmil
95–300 mm
2
840
550
CU30FA4
3
FC
1
#14–#10 Cu
N/A
N/A
#14–#10 STR/SOL
35
4.0
CU100FA
3
FA, FH, FI
1
#14–#1 Cu
2.5–50 mm
2
50
5.7
Cu #3–#1 STR
Cu #6–#4 STR
Cu #8 STR/SOL
Cu #14–#10 STR/
SOL
50
45
40
35
5.7
5.1
4.5
4.0
CU100TF
3
FA, FH
1
#12–#3 Cu
50
5.7
Cu #12–#3 STR
Cu #12–#10 SOL
50
50
5.7
5.7
CU250KA
3
KA, KH, KC, KI
1
#6–#250 MCM Cu
16–20 mm
2
80
9.0
250
22.6
CU400LA
1
Q4, LA, LH
2
#1–#600 MCM Cu
#1–#250 MCM Cu
50–300 mm
2
50–120 mm
2
180
20.0
300
33.9
CU1000MA
1
MA, MH
3
3/0–#500 MCM Cu 95–240 mm
2
300
33.9
300
33.9
CU1200NE6
1
NA, NC
4
3/0–#600 MCM Cu 95–300 mm
2
250
28.2
330
37.3
* STR = Stranded, SOL = Solid