Mammoth V-Cube Slim Split IOM, MAMM-VCS-IOM-3FA (September 2013) 6
Figure 2: Exploded View
FANWALL section
Coil cabinet
End piping
assembly
Filter Rack
Main chassis
Main electrical panel
Mechanical lifting equipment is necessary to dismantle
and relocate the V Cube Slim Split. This unit will weigh
between 4000 and 5800 pounds depending on options
and features built into the unit at the factory.
Mechanical lifting equipment is also required to remove
the sub assemblies from the main chassis. Subassem-
blies weigh a minimum of 205 pounds and as much as
1500 pounds each.
Wiring
NEMA does not allow quick-connect plugs for power (high
voltage) wiring. For this reason, all power wires have raw
ends and are ‘hardwired’ to terminal blocks in the unit and
require handtools for removal. These power wires must
be labeled prior to removal to avoid problems.
All low voltage wires are connected using quick-connect
plugs.
Piping
All water piping is iron with grooved (Victualic
®
) connec-
tions.
Refrigeration circuits are copper pipe and do not require
any disassembly and reassembly.