Fct.

Text

Description and settings

1.06

PULS.OUTP. P

Pulse output P

→

FUNCTION P

Select function for pulse output P
•
OFF (switched off)
• 1 DIR. (1 flow direction)
• 2 DIR. (forward/reverse flow, F/R measurement)

Press

↵

key to transfer to subfunction “SELECT P “.

→

SELECT P

Select pulse type
•
100 Hz

• PULSE/VOL. (pulses per unit volume, flow rate)

• 1000 Hz

• PULSE/TIME (pulses per unit time for 100% flowrate)

Press

↵

key to transfer to subfunction “PULSWIDTH“.

When 100 Hz and 1000 Hz selected, return to
Fct. 1.06 PULS.OUTP. P, pulse width 50% cyclic.

→

PULSWIDTH

Select pulse width
• 50 mSec

• 100 mSec

• 200 mSec • 500 mSec • 1 Sec

Press

↵

key to transfer to subfunction “VALUE P “.

→

VALUE P

Set pulse value per unit volume (appears only when
“PULSE/VOL.“ has been set under “SELECT P“).
• xxxx PulS/m3

• xxxx PulS/Liter

• xxxx PulS/US.Gal

• xxxx PulS/ user unit, factory set is “Liter“ or “US MGal“ (see Fct. 3.05).
Setting range „xxxx“ is dependent on the pulse width and the
full-scale range: P

min

= F

min

/ Q

100%

P

max

= F

max

/ Q

100%

Press

↵

key to return to Fct. 1.06 “PULS.OUTP. P“.

→

VALUE P

Set pulse value per unit time (appears only
when „PULSE/TIME“ has been set under „SELECT P“).
• xxxx PulS/Sec (=Hz)

• xxxx PulS/min

• xxxx PulS/hr

• xxxx PulS/user unit, factory set is “hr“ or “day“ (see Fct. 3.05)
“xxxx“ setting range is dependent on pulse width, see above.

Press

↵

key to return to Fct. 1.06 “PULS.OUTP. P“.

1.07

IND. OUTP. S

Status output S
•
ALL ERROR

• FATAL ERROR

• OFF

• ON

• F/R INDIC. (F/R indication for forward/reverse measurement)
• TRIP. POINT

Setting range: 002 - 115 PERCENT

• EMPTY PIPE (appears only when this option is installed)

(Press

↵

key to transfer to number setting.)

Press

↵

key to return to Fct. 1.07 “IND.OUTP. S“.

Fct.

Text

Description and settings

2.00

TEST

Test menu

2.01

TEST Q

Test measuring range Q
Precautionary query
• SURE NO

Press

↵

key to return to Fct. 2.01 “TEST Q”.

• SURE YES

Press

↵

key, then use

↑

or

↓

key to

select value:

-110 / -100 / -50 / -10 / 0 / +10 / +50 / +100 / +110 PCT.

of set full-scale range Q

100%

.

Displayed value present at outputs I and P.

Press

↵

key to return to Fct. 2.01 “TEST Q”.

2.02

HARDW. INFO

Hardware information and error status
Before consulting factory, please note down all 6 codes.

→

MODUL ADC

X . X X X X X . X X

Y Y Y Y Y Y Y Y Y Y

Press

↵

key to transfer to

“MODUL IO“.

→

MODUL IO

X . X X X X X . X X

Y Y Y Y Y Y Y Y Y Y

Press

↵

key to transfer to

“MODUL DISP.“.

→

MODUL DISP.

X . X X X X X . X X

Y Y Y Y Y Y Y Y Y Y

Press

↵

key to return to Fct. 2.02

“HARDW. INFO“.

Advertising