KROHNE IFC 010 Converter EN User Manual

Page 29

Advertising
background image

5/4

Current output I 5.6

Fct. 1.05 CURRENT I
Press

→

key.

→

FUNCT. I = select function for current output,

press

→

key

•

OFF

(switched off, no function)

•

1 DIR.

(1 flow direction)

•

2 DIR.

(2 flow directions, F/R mode, forward/reverse)

Select using

↑

or

↓

key

.

Transfer to subfunction “RANGE I” with

↵

key.

Exception: When “OFF” selected, return to Fct. 1.05 CURRENT I.

→

RANGE I = select measuring range,

press

→

key

•

0 - 20 mA

fixed ranges

•

4 - 20 mA

Press

→

key to transfer to number setting.

Select with key

↑

or

↓

.

Press key

↵

to transfer to subfunction “I ERROR”.

→

I ERROR = set error value,

press

→

key

•

0

.0

mA

•

3.6 mA

(only possible if range ”4-20 mA” selected)

•

22

.6

mA

Select using key

↑

or

↓

.

Press

→

key to transfer to number setting.

Press key

↵

to return to Fct. 1.05 CURRENT I.

Please refer to Sect. 3.2 “Factory settings”.

Refer to Sect. 2.3 for connection diagrams, and to Sect. 5.14 for characteristics.