5.7 Pulse output P

NOTE! Check whether under Fct. 3.07 “HARDWARE” the output terminal “B1” is defined as
pulse output, refer also to Sect. 2.2 and Sect. 5.16.

Fct. 1.06 PULS.OUTP. P
Press key

.

FUNCT. P = select function for pulse output,

press

key

OFF

(switched off, no function)

1 DIR.

(1 flow direction)

2 DIR.

(2 flow directions, F/R mode, forward/reverse)

Select with key

or

.

Press

key to transfer to subfunction “SELECT P ”.

Exception: When “OFF” selected, return to Fct. 1.06 PULS B1.

SELECT P = select pulse type,

press

key

100 Hz

1000 Hz

PULSE/VOL.

(pulses per unit volume, flow)

PULSE/ZEIT

(pulses per unit time for 100% flow)

Select using

or

key.

Transfer to subfunction ”PULSWIDTH” with

key.

Note: when 100 Hz or 1000 Hz selected, return to Fct. 1.06 PULS.OUTP. P.

PULSWIDTH = set pulse width,

press

key

50 mSec

F

max

= 10 Hz

F

min

= 0.0056 Hz (= 20 Pulse / hr)

100 mSec

= 5 Hz

200 mSec

= 2.5 Hz

500 mSec

= 1 Hz

50

1

m

Sec

= 0,5 Hz

Select using

or

key.

Transfer to subfunction ”VALUE P” with

key or return to Fct. 1.06

PULS.OUT. P, depending on choice of pulse type in subfunction ”SELECT P”.

5/5