KROHNE IFC 010 Converter EN User Manual

Page 34

Advertising
background image

5/9

5.11 Primary head

Please refer to Sect. 3.2 “factory settings”

Fct. 3.02 FLOW METER
Press

→

key.

→

DIAMETER = set meter size (see instrument nameplate)

press

→

key

Select size from table of meter sizes:
•

DN 2.5 - 1000 mm equivalent to

1

/

10

- 40 inch

Select using

↑

or

↓

key.

Transfer to subfunction “FULL SCALE” with

↵

key.

→

FULL SCALE = set full-scale range,

press

→

key.

Set as described in Sect. 5.1.

Transfer to subfunction “GKL VALUE” with

↵

key.

Note: if “VALUE P” is displayed after pressing

↵

key.

PULSE/VOL. is set under Fct. 1.06 PULS.OUTP. P, subfunction “SELECT P”. Because the
full-scale range Q

100%

has been changed, the output frequency (F) of the pulse output is over- or

undershot:

P

min

= F

min

/ Q

100%

P

max

= F

max

/ Q

100%

Change pulse value accordingly, see Sect. 5.7 pulse output P, Fct. 1.06.

→

GKL VALUE = set primary constant GK,

press

→

key.

•

1.0000 - 9.9999 (note information on instrument nameplate, do not change setting !)

Change flashing digit (cursor) with

↑

or

↓

key.

Shift cursor 1 place to right or left with

→

or

←

key.

Transfer to subfunction “FIELD FREQ.” with

↵

key.

→

FIELD FREQ. = set magnetic field frequency,

press

→

key

•

1/6 (1/6 or 1/18 of power frequency, see instrument nameplate, do not change setting)

•

1/18

Select using

↑

or

↓

key.

Transfer to subfunction “FLOW DIR.” with

↵

key.

(only for units with DC power supply, transfer to subfunction “LINE FREQ”).

→

LINE FREQ. = normal line frequency in your country,

press

→

key.

•

50 Hz

Select using the

↑

key.

•

60 Hz

Transfer to subfunction “FLOW DIR.” with

↵

key.

→

FLOW DIR. = set flow direction,

press

→

key.

•

+ DIR.

(for identification of flow direction, see “+” arrow on primary head;

•

- DIR.

for F/R mode, identifies the “positive” flow direction)

Select using the

↑

or

↓

key.

Press

↵

key to return to Fct. 3.02 FLOW METER.

Zero check, see Fct. 3.03 and Sect. 7.1.

}