Press ENTER. The unit will display:

To copy another Memory Module, take the existing
one out, insert the next module to be copied and
press EVENT. This will turn ON the write function.
Press Enter and the second module should be
c o p i e d . Repeat this procedure to copy more modules.

After completing all copies:
- Insert original Memory Module
- Turn OFF AC power to the unit.
- Remove unit from enclosure
- Locate the copy switch and set it to OFF (red

switch labeled BP01)

- Put unit back in enclosure
- Put back insulator that covers the terminal bl o ck .

M a ke sure no terminals are exposed to the opera t or.

- Apply AC power to unit
- Insert the pin in the small pinhole (located in the

upper right hand corner) to rest the unit.

- Set the time and date.

14

CAUTION: DO NOT REMOVE MEMORY MODULE
WHILE UNIT IS AC T I V E . THE UNIT MUST BE
RESET; TIME AND DATE MUST BE RE-ENTERED
TO MAKE SCHEDULE SETTINGS EFFECTIVE ON
THE MEMORY MODULE.

NOTE: AFTER MAKING ANY CHANGES TO THE
PROGRAM, PRESS MODE TO GO TO RUN MODE
AND THEN PRESS EVENT TO UPDATE THE LOAD
STATUS.

INSTRUCTIONS FOR SETTING THE UNIT
Connect unit to main power source prior to entering the
settings. When powering up the unit for the first time,
allow 1-2 minutes for supercap to charge and the display
will show 12 HOUR.

Press HOUR to change to 24 hour (military format) or
Press ENTER to set 12 hour (AM/PM format).

NOTES:
1. During the RUN mode, the Hour, Minutes, Seconds,

Day of week and flashing colons will be displayed.

2. Unit will not go into run mode unless the clock and

date information has been entered. In any other
mode, if no entry is made for 5 minutes, the unit will
automatically revert to the run mode.

3. Unit will display “PF” (Power Failure) in the absence of

AC power. A minimum of 8 hours is required to fully
charge the super cap.

4. When previously programmed unit comes back from

a power failure, it will “look back” and update the
schedule, executing the last scheduled event. If a sig-
nal setting was scheduled, after power failure the unit
will execute the last scheduled signal. Settings can be
manually updated by pressing the EVENT key in the
run mode.

After pressing ENTER the unit will display:

3

NOTE: AFTER MAKING ANY CHANGES TO THE
PROGRAM, PRESS MODE TO GO TO RUN MODE
AND THEN PRESS EVENT TO UPDATE THE LOAD
STATUS.