8100serieswiring, Tork electromechanical, Variable cycling timers – NSi Industries 8001 User Manual

Page 9: Tork, 8000 series, Applications, Specifications, Specification writer’s guide, Ordering information

Advertising
background image

TORK ELECTROMECHANICAL

TORK

1 Grove St., Mt. Vernon, NY 10550 • Tel: 914-664-3542 • Fax: 914-664-5052 • Internet: http://www.tork.com

VARIABLE CYCLING TIMERS

8000 SERIES

APPLICATIONS

For one to many daily ON-OFF operations

Duty Cycling

Ventilating Fans

Pumping

Irrigation

Process Control

Laboratory Experiments

SPECIFICATIONS

Contact Ratings: 20 Amps at 120 or 240V, 5 Amps at
480V, 3/4 HP at 120V AC

Timing Motor: Heavy duty synchronous, self-starting, high
torque. Power Consumption: 3 watts.

Dial: Captivated tabs for setting are easily tilted in or out by
hand. Switch stays ON or OFF as set when adjacent tabs
are set alike.

60 Minute Duty Cycle Dial

1 to 30 ON-OFF operations per hour, 60 tabs permit 1
minute switching changes. Total Duty Cycle adjustable from
2, 3, 4, 5, 6, 10, 12, 15, 20, 30, or 60 minutes with 1 minute
minimum ON and/or OFF settings.

30 Minutes, 12 Minutes, 6 Minutes, and 1 Minute Dials

60 tabs available with minimum ON or OFF settings of
1/60th of dial speed.

Operating Temperature Range: -40° to +165°F. (-40° to
+74°C.)

Enclosures:

See end of controls section for dimensions.

General purpose (NEMA 1). Drawn steel, beige enamel,
with combination 1/2” and 3/4” K.O.’s on sides, bottom and
back. Lockable hasp. Cover is removable and movement
releases from case at finger touch for easy installation.

Other Mountings:

Model IAP-Intermatic

®

Adapter Plate – allows any TORK

8000 model to fit into an Intermatic case without necessity
of changing the enclosure.

Flush, with lock and key (suffix FL1) – Model 9001*

Duplex – 2 standard units in one indoor/outdoor case,
(except 3 pole) surface (suffix DUOL) – Model 9004L*

Noryl

®

Indoor/Outdoor– NEMA 3R (suffix N) – Model

9000N.*

Metal Indoor/Outdoor – NEMA 3 (suffix O) – Model
9000A* (hinged side)

Bracket mounting – specify mechanism only, with bracket.

*Use model number when ordering special enclosures separately.

SPECIFICATION WRITER’S GUIDE

The repeating timer shall be of the program tab-type, capable of program-
ming in increments of 1/60 of one dial rotation. Program tabs shall be cap-
tive on dial and shall be easily set by hand without tools to obtain or change
the desired programming schedule. The switching condition shall be main-
tained when adjacent tabs are set alike. The unit shall be powered with a
self-starting, enclosed 120 (or 208-277) volt, synchronous motor capable
of continuous accurate operation. The switch mechanism shall be a self-
contained unit rated at not less than 20 amperes, 240 volt AC, SPDT, and
shall be readily replaceable in the field. OPTION 1: Unit shall be furnished
less case with mounting bracket (for mounting in control panel). OPTION
2: Enclosure shall be NEMA 1 surface with combination 1/2" and 3/4"
knockouts on bottom, both sides, top and back (or see other mountings).
There shall be at least 25 cubic inches of available space at bottom of
enclosure to facilitate wiring. A slip-out arrangement will be included
to permit prompt removal of the time switch mechanism. Provision
shall be made for positive padlocking and/or sealing. Repeating timer
shall complete one dial rotation in minute(s) and shall be TORK
Model 8 _ _ _ (to fit requirement).

MOTOR

H.P

Model #

Switch

Type

Amps

Rating

AC Voltage

Hz

8601

SPDT

60 Minute

20

3/4

120

60

8602

SPDT

60 Minute

20

1-1/2

208-277

60

8301

SPDT

30 Minute

20

3/4

120

60

8121

SPDT

12 Minute

20

3/4

120

60

8061

SPDT

6 Minute

20

3/4

120

60

8011

SPDT

1 Minute

20

3/4

120

60

H

120VAC

N

C

L

2

NO

NC

LOAD 2

MOTOR

LOAD 1

CLOSED WITH

TAB INWARD

CLOSED WITH

TAB OUTWARD

Reserve Power is not available in this series.