3.3.3

Setpoint Parameters

3.3.4

Alarm Parameters

For descriptions of the operation of the different alarm types, see Figure 2-3.

O054-3

3-7

59125

Parameter

Identifier

Description

Setpoint

value

S

May be read (Type 2 message) or modified (Type

3/Type 4 message sequence). Limited by Setpoint High

Limit and Setpoint Low Limit (see below).

Setpoint

Ramp Rate

^

May be read (Type 2 message) or modified (Type

3/Type 4 message sequence). May be set in the range

1 - 9999 increments/hour or OFF ({DATA} =0000).

Decimal point position is as for input range.

Setpoint High

Limit

A

May be read (Type 2 message) or modified (Type

3/Type 4 message sequence). Defines maximum value

for setpoint (in the range setpoint - Input Range

Maximum). Decimal point position is as for input

range.

Setpoint Low

Limit

T

May be read (Type 2 message) or modified (Type

3/Type 4 message sequence). Defines minimum value

for setpoint (in the range Input Range Minimum -

setpoint). Decimal point position is as for input range.

Parameter

Identifier

Description

Alarm 1 value

C

May be read/modified by a Type 2 message or a

Type 3/Type 4 message sequence. Decimal point

position is as for input range.

Alarm 2 value

E

May be read/modified by a Type 2 message or a

Type 3/Type 4 message sequence. Decimal point

position is as for input range.