Tuning parameters, Rate (derivative time constant), Reset (integral time constant) – West Control Solutions N8100 User Manual

Page 34: Manual reset (bias), On/off differential, Proportional band 1 value, Proportional band 2 value

Advertising
background image

3.3.5

Tuning Parameters

3-8

O054-3

59125

Parameter

Identifier

Description

Rate (Derivative

Time Constant)

D

May be read/modified using a Type 2 message or a

Type 3/Type 4 message sequence. Defines the

derivative time constant for the control algorithm.

{DATA} is of the form mm.ss where mm = minutes

and ss = seconds. The decimal point position must

specify two decimal places, otherwise modification

will not occur.

Reset (Integral

Time Constant)

I

May be read/modified using aType 2 message or a

Type 3/Type 4 message sequence. Defines the

integral time constant for the control algorithm.

{DATA} is of the form mm.ss where mm = minutes

and ss = seconds. The decimal point position must

specify two decimal places, otherwise modification

will not occur.

1

Manual Reset

(Bias)

J

May be read/modified using a Type 2 message or a

Type 3/Type 4 message sequence. Decimal point

position is as for input range.

ON/OFF

Differential

F

May be read/modified using a Type 2 message or a

Type 3/Type 4 message sequence. Defines the

switching hysteresis for controllers with an ON/OFF

control output. Decimal point position = 1.

Overlap

/Deadband

K

May be read/modified using a Type 2 message or a

Type 3/Type 4 message sequence. May be set to a

positive (overlap) or negative (deadband) value.

Decimal point position = 0.

2

Proportional

Band 1 value

P

May be read/modified using a Type 2 message or a

Type 3/Type 4 message sequence. May be set to

0.0 (ON/OFF control) or within the range 0.5% -

999.9% of Output 1 power range. Decimal point

position = 1.

Proportional

Band 2 value

U

May be read/modified using a Type 2 message or a

Type 3/Type 4 message sequence. May be set to

0.0 (ON/OFF control) or within the range 0.5% -

999.9% of Output 2 power range. Decimal point

position = 1.

2

Advertising