3.3.6

Status Parameters

3.3.7

Controller Commands

O054-3

3-9

59125

Parameter

Identifier

Description

Controller

Status

L

Read Only (Type 2 message). Status information is

encoded in four digits as the decimal representation of a

binary number; each bit in the binary number has a

particular significance (see Figure 3-1 ).

Arithmetic

Deviation

V

Read Only (Type 2 message). The difference between the

process variable value and the Limit Setpoint value.

Scan

Tables

]

Read Only (Type 2 message). Response:

L{N}xxaaaaabbbbbcccccdddddeeeeeA*

where:

xx =

Number of data digits in {DATA}

element (20 for single control output,

25 for dual control outputs)

aaaaa = Current setpoint value

bbbbb =

Current process variable value

ccccc =

Current value of Output 1 Power

(0 - 100%)

ddddd =

Current value of Output 2 Power

(0 - 100%) - if applicable.

eeeee =

Controller Status (see Figure 3-1)

Parameter

Identifier

Description

Controller

Commands

Z

Implemented by Type 3/Type 4 message sequence only.

In the Type 3 message, {DATA} must be one of eight

five-digit numbers:

00010

Activate Manual Control

00020

Activate Automatic Control

00030

Activate Self-Tune

00040

De-activate Self-Tune

00050

Request Pre-Tune*

00060

Abort Pre-Tune

00130

Activate Loop Alarm

00140

De-activate Loop Alarm

The response from the Controller also contains the same

{DATA} content, as does the response to the Type 4

message.