4 error list / mainenance manager 14 – West Control Solutions N8800 User Manual

Page 14

Advertising
background image

Operation

Error list / Mainenance manager

14

8800 process controller

Name

Description

Reason

Possible remedial action

HCA

Heating current

alarm (HCA)

- Heating current circuit

interrupted, I< HC.A or

I> HC.A (dependent of

configuration)

- Heater band defective

- Check heating current circuit

- If necessary, replace heater band

SSr

Heating current

short circuit (SSR)

- Current flow in heating

circuit with controller

off

- SSR defective

- Check heating current circuit

- If necessary, replace solid-state relay

LooP

Control loop alarm

(LOOP)

- Input signal defective or

not connected correctly

- Output not connected

correctly

- Check heating or cooling circuit

- Check sensor and replace it, if

necessary

- Check controller and switching

device

AdA.H

Self-tuning heating

alarm

(ADAH)

- See Self-tuning heating

error status

- see Self-tuning heating error status

AdA.C

Self-tuning heating

alarm cooling

(ADAC)

- See Self-tuning cooling

error status

- see Self-tuning cooling error status

LiM.1

stored limit alarm 1 - adjusted limit value 1

exceeded

- check process

Lim.2

stored limit alarm 2 - adjusted limit value 2

exceeded

- check process

Lim.3

stored limit alarm 3 - adjusted limit value 3

exceeded

- check process

Inf.1

time limit value

message

- adjusted number of

operating hours reached

- application-specific

Inf.2

duty cycle message

(digital ouputs)

- adjusted number of duty

cycles reached

- application-specific

E.5

Internal error in DP

module

- self-test error

- internal communication

interrupted

- Switch on the instrument again

- Contact West service

dp.1

No access by bus

master

- bus error

- connector problem

- no bus connection

- Check cable

- Check connector

- Check connections

dp.2

Faulty configuration - Faulty DP

configuration telegram

- Check DP configuration telegram in

master

dp.3

Inadmissible

parameter setting

telegram sent

- Faulty DP parameter

setting telegram

- Check DP parameter setting

telegram in master

dp.4

No data

communication

- Bus error

- Address error

- Master stopped

- Check cable connection

- Check address

- Check master setting

Advertising