3.7 Second PID parameter set

The process characteristic is frequently affected by various factors such as

process value, correcting variable and material differences.

To comply with these requirements, the 8800 process controller can be switched

over between two parameter sets.

Parameter sets PArA and PAr.2 are provided for heating and cooling.

Dependent of configuration ( ConF/LOG/Pid.2), switch-over to the second

parameter set ( ConF/LOG/Pid.2) is via one of digital inputs di1, di2, di3,

key è or interface (OPTION).

g

Self-tuning is always done using the active parameter set, i.e. the second

parameter set must be active for optimizing.

Operation

8800 process controller

25

Second PID parameter set

Formulas

K = Vmax * Tu

controller behavior

Pb1 [phy. units]

td1 [s]

ti1 [s]

With 2-point and

3-point controllers,

the cycle time must be

adjusted to

t1 / t2 ≤ 0,25 * Tu

PID

1,7 * K

2 * Tu

2 * Tu

PD

0,5 * K

Tu

OFF

PI

2,6 * K

OFF

6 * Tu

P

K

OFF

OFF

3-point-stepping

1,7 * K

Tu

2 * Tu

Parameter adjustment effects

Parameter Control

Line-out of disturbances

Start-up behaviour

Pb1 highe

r

increased damping slower line-out

slower reduction of duty cycle

lower reduced damping faster line-out

faster reduction of duty cycle

td1 highe

r

reduced damping faster response to disturbances faster reduction of duty cycle

lower increased

damping

slower response to

disturbances

slower reduction of duty cycle