Configuration 41 – West Control Solutions N8800 User Manual

Page 41

Advertising
background image

Configuration level

8800 process controller

41

Configuration parameters

Name

Value range Description

Default

Y.1

Controller output Y1 (only visible when O.TYP=0)

0

0

not active

1

active

Y.2

Controller output Y2 (only visible when O.TYP=0)

0

0

not active

1

active

Lim.1

Limit 1 signal (only visible when O.TYP=0)

0

0

not active

1

active

Lim.2

Limit 2 signal (only visible when O.TYP=0)

0

0

not active

1

active

Lim.3

Limit 3 signal (only visible when O.TYP=0)

0

0

not active

1

active

dAc.A

Valve monitoring (DAC) (only visible when O.TYP=0)

0

0

not active

1

active

LP.AL

Interruption alarm signal (LOOP) (only visible when

O.TYP=0)

0

0

not active

1

active

HC.AL

Heat current alarm signal (only visible when O.TYP=0)

0

0

not active

1

active

HC.SC

Solid state relay (SSR) short circuit signal (only visible

when O.TYP=0)

0

0

not active

1

active

FAi.1

INP1 error (only visible when O.TYP=0)

0

0

not active

1

active

FAi.2

INP2 error (only visible when O.TYP=0)

0

0

not active

1

active

FAi.3

INP3 error (only visible when O.TYP=0)

0

0

not active

1

aktiv

Out.0

-1999...9999

Scaling of the analog output for 0% (0/4mA or 0/2V, only

visible when O.TYP=1..5)

0

Out.1

-1999...9999

Scaling of the analog output for 100% (20mA or 10V, only

visible when O.TYP=1..5)

100