Configuration level

Configuration parameters

40

8800 process controller

Name

Value range Description

Default

FAi.1

INP1 error (only visible when O.TYP=0)

1

0

not active

1

active

FAi.2

INP2 error (only visible when O.TYP=0)

0

0

not active

1

active

FAi.3

INP3 error (only visible when O.TYP=0)

0

0

not active

1

aktiv

Out.0

-1999...9999

Scaling of the analog output for 0% (0/4mA or 0/2V, only

visible when O.TYP=1..5)

0

Out.1

-1999...9999

Scaling of the analog output for 100% (20mA or 10V, only

visible when O.TYP=1..5)

100

O.Src

Signal source of the analog output OUT3 (only visible when

O.TYP=1..5)

1

0

not used

1

controller output y1 (continuous)

2

controller output y2 (continuous)

3

process value

4

effective set-point Weff

5

control deviation xw (process value - set-point)

6

measured value position feedback Yp

7

measured value INP1

8

measured value INP2

9

measured value INP3

fOut

Forcing OUT3 (only visible with 8800/8840 configurator!)

0

0

No forcing

1

Forcing via serial interface

Out.4

Name

Value range Description

Default

O.tYP

Signal type selection OUT4

0

0

relay / logic (only visible with current/logic voltage)

1

0 ... 20 mA continuous (only visible with

current/logic/voltage)

2

4 ... 20 mA continuous (only visible with

current/logic/voltage)

3

0...10 V continuous (only visible with current/logic/voltage)

4

2...10 V continuous (only visible with current/logic/voltage)

5

transmitter supply (only visible without OPTION)

O.Act

Method of operation of output OUT4 (only visible when

O.TYP=0)

0

0

direct / normally open

1

inverse / normally closed