3.5 Maintenance manager / Error list

With one or several errors, the extended operating level al-
ways starts with the error list. Signalling an actual entry in
the error list (alarm, error) is done by the Err LED in the
display. To reach the error list press Ù twice.

Err LED status

Signification

Proceed as follows

blinks

Alarm due to existing error

- Determine the error type in the error list

via the error number

- Remove the error

lit

Error removed,
Alarm not acknowledged

- Acknowledge the alarm in the error list

pressing key È or Ì

- The alarm entry was deleted.

off

No error,
all alarm entries deleted

Error list:

Name

Description

Cause

Possible remedial action

E.1

Internal error,
cannot be removed

- E.g. defective EEPROM - Contact PMA service

- Return unit to our factory

E.2

Internal error, can be

reset

- e.g. EMC trouble

- Keep measurement and power

supply cables in separate runs

- Ensure that interference

suppression of contactors is
provided

FbF.1

Sensor break INP1

- Sensor defective
- Faulty cabling

- Replace INP1 sensor
- Check INP1 connection

Sht.1

Short circuit INP1

- Sensor defective
- Faulty cabling

- Replace INP1 sensor
- Check INP1 connection

POL.1

INP1polarity error

- Faulty cabling

- Reverse INP1 polarity

Lim.1

Stored LC alarm

- adjusted limit value LC

exceeded

- check process

Lim.2

Stored alarm 2

- adjusted limit value

alarm 2 exceeded

- check process

Lim.3

Stored alarm 3

- adjusted limit value

alarm 3 exceeded

- check process

Inf.1

time limit value

message

- adjusted number of

operating hours reached

- application-specific

Operation

Maintenance manager / Error list

10

TB40-1

125