5 parameter setting level 18, 1 parameter survey 18, 2 parameters 18 – West Control Solutions TB 40-1 Temperature Limiter User Manual

Page 18: Parameter setting 18, Parameter setting level 18 - 19, Inp.1, 5parameter setting level 5.1 parameter survey, 2 parameters, Parameter setting level

Advertising
background image

5

Parameter setting level

5.1 Parameter survey

PArA

Parameter setting level

И

М

Lim

Limit

value

functions

InP.1

Input

1

rnG

LC

setting

range

End

LC

InL.1 rnGL

L.2

OuL.1 rnGH

H.2

InH.1

HYS.2 OuH.1
L.3

tF.1

H.3

HYS.3

g

Adjustment:

w The parameters can be adjusted by means of keys ÈÌ

w Transition to the next parameter is by pressing key Ù

w After the last parameter of a group, donE is displayed, followed by

automatic change to the next group.

+

Return to the beginning of a group is by pressing the

Ù key for 3 sec.

5.2 Parameters

Lim

Name

Value range Description

Default

LC

-1999...9999

LC limit

100

L.2

-1999...9999

Lower limit 2

OFF

H.2

-1999...9999

Upper limit 2

OFF

HYS.2

0...9999

Hysteresis limit 2

1

L.3

-1999...9999

Lower limit 3

OFF

H.3

-1999...9999

Upper limit 3

OFF

HYS.3

0...9999

Hysteresis limit 3

1

L.3, H.3, Hys.3 only available if Fcn.1= TW

InP.1

Name

Value range Description

Default

InL.1

-1999...9999

Input value for the lower scaling point

0

OuL.1

-1999...9999

Displayed value for the lower scaling point

0

InH.1

-1999...9999

Input value for the upper scaling point

20

OuH.1

-1999...9999

Displayed value for the upper scaling point

20

t.F1

-1999...9999

Filter time constant [s]

0,5