3 input scaling inp.1 19, Input scaling 19, 3 input scaling inp.1 – West Control Solutions TB 40-1 Temperature Limiter User Manual

Page 19: Parameter setting level

Advertising
background image

rnG

Name

Value range Description

Default

rnG.L

-1999...9999

Set-point limit low for set-point LC

-1999

rnG.H

-1999...9999

Set-point limit high for set-point LC

9999

g

Resetting the device configuration to factory setting (Default)

r chapter 10.1 (page 30)

5.3 Input scaling

InP.1

When using current or voltage signals as input variables for

InP.1 scaling of

input and display values at parameter setting level is required. Specification of
the input value for lower and higher scaling point is in the relevant electrical unit
(mA/ V).

g

Parameters

InL.1 , OuL.1, InH.1 and OuH.1 are only visible if

ConF / InP.1 / Corr = 3 is chosen.

S.tYP

Input signal

InL.1

OuL.1

InH.1

OuH.1

30

(0...20mA)

0 … 20 mA

0

any

20

any

4 … 20 mA

4

any

20

any

40

(0...10V)

0 … 10 V

0

any

10

any

2 … 10 V

2

any

10

any

In addition to these settings,

InL.1 and InH.1 can be adjusted in the range

(0...20mA / 0...10V) determined by selection of

S.tYP .

a

For using the predetermined scaling with thermocouple and resistance
thermometer (Pt100), the settings for

InL.1 and OuL.1 and for InH.1 and

OuH.1 must have the same value.

g

Input scaling changes at calibration level (r page 20) are displayed by input
scaling at parameter setting level. After calibration reset (

OFF), the scaling

parameters are reset to default.

Parameter setting level

TB40-1

19

Input scaling

InP.1

mA/V

phys.

quantity

mA / V

phys. quantity

OuH.x

OuL.x

InH.x

InL.x