9

Technical data

INPUTS

PROCESS VALUE INPUT INP1

Resolution:

> 14 bits

Decimal point:

0 to 3 digits behind the decimal point

Dig. input filter:

adjustable 0,000...9999 s

Scanning cycle:

100 ms

Measured value
correction:

2-point or offset correction

Thermocouples

r

Table 1 (page 27 )

If the device is used as a teperature limiter, a
double thermocouple must be connected. For
measurements in the area of ambient
temperature (0mV) the plausibility is ensured
by the control of the 2nd thermocouple.
Outside of this range there is no check of the
2nd thermocouple.

Input resistance:

³ 1 MW

Effect of source resistance:

1

mV/W

Cold-junction compensation

Maximal additional error:

± 0,5 K

Sensor break monitoring

Sensor current:

£1 mA

Configurable output action

Resistance thermometer

r

Table 2 (page 27 )

Connection:

2 or 3-wire

Lead resistance:

max. 30 Ohm

Input circuit monitor:

break and short circuit

Special measuring range
BlueControl (engineering tool) can be used to
match the input to sensor KTY 11-6
(characteristic is stored in the controller).

Physical measuring range:

0...4500 Ohm

Linearization segments

16

Current and voltage signals

r

Table 3 (page 27 )

Span start, end of span: anywhere within measuring range
Scaling:

selectable -1999...9999

Linearization:

16 segments, adaptable with
BlueControl

Decimal point:

adjustable

Input circuit monitor:

12,5% below span start (2mA, 1V)

CONTROL INPUT DI1

Configurable as switch or push-button!
Connection of a potential-free contact suitable
for switching “dry” circuits.

Switched voltage:

2,5 V

Current:

50

mA

GALVANIC ISOLATION

Safety isolation
Function isolation

OUTPUTS

OUTPUT LC

Function:
Interruption of the power supply if the set limit
is exceeded or fallen short.

Contact type:

potential-free changeover contact

Max.contact rating:

500 VA, 250 V, 2A at 48...62 Hz,
resistive load

Min. contact rating:

5V, 10 mA AC/DC

Operating life (electr.):

600.000 duty cycles with max.
contact rating

If the device is used as temperature limiter
(configuration date

Fcn.1 = 7 or 8) the bridge

between clamps 6 and 7 must not be removed!
The bridge ensures the safe interruption of power by
serial switching of the relays LC and OUT2. If the
device is utilized as temperature monitor
(configuration date Fcn.1 = 5 or 6) the bridge
can be removed, the break is only via LC relay

OUTPUTS OUT1, OUT2

Function:
Additional alarms with MAX, MIN or MAX+MIN
monitoring with adjustable hysteresis.
Monitored signals:

w

process value (absolut)

w

difference to the limit (relative)

w

sensor break / short circuit

According to the input type, the input signal is
monitored to sensor break, polarity error and
short circuit

Technical data

TB40-1

25

Power supply connections Process value input INP1

Digital input di1

Relay outputs OUT 1,2
Relay output OUTLC