Functions 21, 1 limiting functions 21, 1 temperature monitor 21 – West Control Solutions TB 45 Temperature Monitor User Manual

Page 21: 2 limit signaller 21, Functions 21 - 32, Functions 6.1, 6 functions

Advertising
background image

.

6

Functions

The signal data flow of temperature monitor TB 45 is shown in the following diagram:

6.1

Limiting functions

TB 45 can be configured for various functions:

as a temperature monitor

as a limit signaller

6.1.1

Temperature monitor

The selected temperature monitor function monitors the process value. When the process value is above the adjusted
high limit value LC or below the adjusted low limit value LC (configurable), output relay LC is opened and disabled.

Release is automatic, when

– the process value is below the adjusted high limit value LC (minus any adjusted hysteresis) again with setting

”Temperature monitor max.”, or when the process value is above the adjusted low limit value LC (plus any
adjusted hysteresis) again with setting “Temperature monitor min.”.

g

When display element TB is lit, a temperature monitor function is selected.

a

Please, note that the adjusted filter time

t.F1 can increase the response time for the process value. The

DIN-tested response times were tested with t.F1 = 0,5 s.

Limit values Lim.2, Lim.3 can be used as pre-alarms for (optional) output on OUT.2, OUT.3.

6.1.2

Limit signaller

A selected limit signalling function monitors the process value. When exceeding the adjusted limit values L.1 / H.1 ,
output relay LC is opened (see also chapter Limit values!)
Limit values Lim.2, Lim.3 can be used as pre-alarms for (optional) output on Out.2, Out.3.

Functions

TB 45

Limiting functions

21