1 offset correction 43, Offset-correction 43, Offset correction – West Control Solutions TB 45 Temperature Monitor User Manual
Page 43

9.1
Offset correction
The offset-correction shifts the input value by a pre-defined value.
Parameter setting:
(
ConF/ InP/ Corr =1 )
w
On-line offset correction at the process is
possible.
InL:
The actual input value of the scaling point is displayed.
The correction function is activated by means of keys ÈÌ ; the display changes from Off to
the measured value.
The operator must wait, until the process is at rest.
Subsequently, the input value has to be confirmed by pressing key ô .
OuL:
The scaling point display value is indicated.
The operator can correct the display value by pressing keys ÈÌ.
Subsequently, he presses key ô to confirm the display value.
Calibrating level
TB 45
Offset correction
43