Control input di1 (reset), Outputs relay outputs lc, out2, Out3 as universal output (option) – West Control Solutions TB 45 Temperature Monitor User Manual

Page 48

Advertising
background image

Technical data

48

TB 45

CONTROL INPUT DI1 (RESET)

Configurable as direct or inverse switch or push button!

Contact input

Connection of potential-free contact that is suitable for switching
‘dry’ circuits.

Switched voltage:

5 V

Switched current:

1 mA

Optocoupler input

Actively switched optocoupler input

Nominal voltage:

24 V DC external

Logic ”0”:

-3 V…+5 V

Logic ”1”:

15 V…30 V

Current demand:

max. 6 mA

OUTPUTS

RELAY OUTPUTS LC, OUT2

Type:

2 NO contacts with a common terminal

Max. contact rating:

500 VA, 250 VAC, 2A at 48...62 Hz,
resistive load

Min. contact rating:

6V, 1 mA DC

Switching cycles

(electrical):

for I=1A/2A: ?

800.000/500.000 (at

250VAC, resistive load)

Note:

If the relays LC and OUT2 operate external contactors, these must
be fitted with RC snubber circuits to manufacturer specifications
to prevent excessive voltage peaks at switch-off.

OUT3 AS UNIVERSAL OUTPUT (OPTION)

Galvanically isolated from the inputs. Parallel current/voltage
output with common ‘minus’ terminal (combined use only in
galvanically isolated circuits).

Freely scalable
Resolution:

14 bits

Dynamic response (step change of
input signal) T

90

:

Output follows the input:

ß

540 ms

Tracking error I/U

:

ß

2 %

Residual ripple: (referred to end of
span)

ß_1%
0...130 kHz

Current output

0/4...20 mA, configurable

short-circuit proof

Control range:

-0,5...23 mA

Load:

ß 700 [

Type

Sensor current

Measuring range

Accuracy

Resolution (Ô)

Pt100***

ß 0,25 mA

-200...100 (150) °C

-328...212°F

ß 1 K

0,1 K

0,1 K

0,1 K

Pt100

-200...850°C

-328...1562°F

ß 1 K

Pt1000

-200...850°C

-328...1562°F

ß 2 K

KTY 11-6*

-50...150°C

-58...302°F

ß 2 K

0,1 K

Special

*

0...4500 [**

Я 0,1 %
Я 0,1 %
Я 0,1 %
Я 0,1 %
Я 0,1 %

0,01 %
0,01 %
0,01 %
0,01 %
0,01 %

Special

0...450 [**

Poti

0...160 [**

Poti

0...450 [**

Poti

0...1600 [**

Poti

0...4500 [**

* Default setting is the characteristic for KTY 11-6 (-50...150°C)
** Including lead resistance
*** Up to 150°C with reduced lead resistance (max. 160

[ total)

Table 2: Resistive inputs

Measurement range

Input resistance

Accuracy

Typical resolution

0...20 mA

20 [

ß 0,1 %

1,5

mA

0...10 V

» 110 k[

ß 0,1 %

0,6 mV

-10...10 V

» 110 k[

ß 0,1 %

1,2 mV

-5...5 V

» 110 k[

ß 0,1 %

0,6 mV

-2,5...115 mV*

> 1 M[

ß 0,1 %

6,0

mV

-25...1150 mV*

> 1 M[

ß 0,1 %

60,0

mV

-25...90 mV*

> 1 M[

ß 0,1 %

8,0

mV

-500...500 mV*

> 1 M[

ß 0,1 %

80,0

mV

-200...200 mV*

> 1 M[

ß 0,1 %

40,0 mV

* For INP1: high-impedance, without break monitoring

Table 3: Current and voltage input