7.2

Configuration

Dependent on instrument version and configuration settings, display of values which are not required is suppressed.

µ The entries marked with this symbol are selectable only, if the instrument option is fitted.

Functions Func

Name

Value range Description

Fnc.1

Function 1

0

Standard (measured value = INP1)

2

The measured value is calculated as the difference of the two values (INP1 - INP2).

µ

3

Maximum value of INP1 and INP2. The higher one of the two values is used. With sen-
sor error, the remaining value is used.

µ

4

Minimum value of INP1 and INP2. The smaller one of the two values is used. With
sensor error, the remaining value is used.

µ

7

O2 function with constant sensor temperature. The unit for the O2 settings can be
checked in Others ->

Parameter unit

(ppm / %). The sensor temperature must be speci-

fied in Parameters -> Controller (version-dependent: Function) -> Probe temperature.

µ

8

O2 function with measured sensor temperature. The sensor temperature as a second
measured value INP2 is required. The unit for the O2 settings must be checked in Ot-
hers -> Parameter unit (ppm / %).

µ

Inputs InP.1 and InP.2 (

µ)

Name

Value range Description

I.Fnc

Input function (

µ with 2nd universal input only )

0

No measurement

1

measurement

S.tYP

Sensor type

0

Thermocouple type L (-100...900°C), Fe-CuNi DIN

1

Thermocouple type J (-100...1200°C), Fe-CuNi

2

Thermocouple type K (-100...1350°C), NiCr-Ni

3

Thermocouple type N (-100...1300°C), Nicrosil-Nisil

4

Thermocouple type S (0...1760°C), PtRh-Pt10%

5

Thermocouple type R (0...1760°C), PtRh-Pt13%

6

Thermocouple type T (-200...400°C), Cu-CuNi

7

Thermocouple type C (0...2315°C), W5%Re-W26%Re

8

Thermocouple type D (0...2315°C), W3%Re-W25%Re

9

Thermocouple type E (-100...1000°C), NiCr-CuNi

10

Thermocouple type B (0/100...1820°C), PtRh-Pt6%

18

Special thermocouple (linearization necessary)

20

Pt100 (-200.0 ... 100,0 °C) (150°C with reduced lead resistance)

21

Pt100 (-200.0 ... 850,0 °C)

22

Pt1000 (-200.0...850.0 °C)

23

Special 0...4500 Ohm (preset KTY11-6)

24

Special 0...450 Ohm

25

Special 0...1600 Ohm

26

Special 0...160 Ohm

30

0...20mA / 4...20 mA

40

0...10V / 2...10 V (Inp.1 only)

41

Special (-2,5...115 mV)

42

Special (-25...1150 mV)

43

Special (-25...90 mV)

44

Special (-500...500 mV)

45

Special (-5...5 V) (Inp.1 only)

46

Special (-10...10 V) (Inp.1 only)

Configuration level

34

Configuration

TB 45