West Control Solutions CALogix User Manual

Page 10

Advertising
background image

EXAMPLE CIRCUIT
The circuit below shows an example applicaion which includes a base-unit that has one PID module and one logic module
fitted.


































FS1 Fuse = 1A time lag type to IEC127. CSA/UL rating 250V
FS2 Fuse = 2A time lag type to IEC127. CSA/UL rating 250V
FS3 Fuse = High rupture capacity (HRC). Suitable for maximum rated load current

S1 switch = IEC/CSA/UL approved disconnection device must be used



It is strongly recommended that the power supply zero volts and all logic module zero volts are common to prevent ground
loops.

INPUT SENSOR SELECTION









* Note

: Type-B accuracy not specified below 100°C/212°F

Thermocouple type

Description

Sensor Range (°C)

Sensor Range (°F)

B

Pt-30% Rh/Pt-6%Rh

0 to1800°C*

32 to 3272°F*

E

Chromel/Con

0 to 600°C

32 to 1112°F

J

Iron/Constantan

0 to 800°C

32 to 1472°F

K

Chromel/Alumel

-50 to 1200°C

-58 to 2192°F

L

Fe/Konst

0 to 800°C

32 to 1472°F

N

Nicrosil/NiSil

-50 to 1200°C

-58 to 2192°F

R

Pt-13%Rh/Pt

0 to 1600°C

32 to 2192°F

S

Pt10%Rh/Pt

0 to 1600°C

32 to 2192°F

T

Copper/Con

-200 to 250°C

-273 to 482°F

Resistance Thermometer

rtd 2/3 wire

Pt100/RTD-2/3

-200 to 800°C

-273 to 1472°F

Page 10 of 44