West Control Solutions CALogix User Manual

Page 23

Advertising
background image

Change setpoint 2 value


Band

2

-9999 to 9999 step 0.01

SP2 proportional band or Hysteresis -

* 100% sensor maximum, proportional control eliminates the cycling of on-off control. Output power

is varied, by proportioning action, across the proportional band


Integral time

5 mins

0 to 1000, step 0.1

SP2 integral time/reset -

Auto-corrects proportional control offset error


Derivative time

25 secs

0 to 200. step 1

SP2 derivative time/rate -

Suppresses overshoot and speeds response to disturbances


DAC

2

0 to 5 step 0.5

SP2 derivative approach control dAC -

Tunes warm-up characteristics, independent of normal operating conditions, by adjusting

when derivative action starts during start-up (smaller dAC value = nearer setpoint).


Derivative sensitivity

0.5

0.1 to 1, step 0.1


Cycle time

10 secs

0.1 to 9.9, step 0.1

10

to

81,

step

1

SP2 proportional cycle-time -

Determines the cycle rate of the output device for proportional control.

The choice of cycle-time is influenced by the external switching device or load. eg. contactor, SSR, valve. A setting that is too long for the
process will cause oscillation and a setting that is too short will cause unnecessary wear to an electro-mechanical switching
device.


Maximum power

100

0 to 100, step 1

Maximum % proportional output of SP2. When using proportional control the output of SP3 will not exceed maximum power setting.


Minimum Power

0

0 to 100, step 1

Minimum proportional output of SP2. When proportional control is used the output of SP3 will not reduce below the minimum power setting.


Output power

Read Only

0 to 100, step 1

The current proportional output of SP2 shown as %.


Manual power

Off

Off, 0 to 100, step 1

Manual power overrides PID calculated power output. The proportional output for SP1 will remain constant at the entered value. To return to
PID control set manual power to 0.


Display alarm

No

No,

Yes

When set to yes, alarm symbol is shown on controller image within CALogix-sw when an alarm output is switched.

Reset latched alarm

No

No,

Yes

Used to clear a latched alarm output on SP2, once the alarm condition has cleared. Set value to yes to clear.


Module * - Setpoint 3 control

Default

Options


Operating mode

None

DVHI, DVLO, BAND, FSHI, FSLO, EOP, None


Mode

PARK

P, PARK, On/Off

Primary control type for setpoint 3

P Proportional

Park

Holds

controller

operation

On/Off

On/Off

Control



Subsidiary mode

None

LTCH,

HOLD,

LTHO


Setpoint

3 0

-9999 to 9999, step 0.01

Change setpoint 3 value


Band

2

-9999 to 9999, step 0.01

SP3 proportional band or Hysteresis -

* 100% sensor maximum, proportional control eliminates the cycling of on-off control. Output power

is varied, by proportioning action, across the proportional band


Cycle time

10

0.1 to 9.9, step 0.1

10

to

81,

step

1

SP3 proportional cycle-time -

Determines the cycle rate of the output device for proportional control.

The choice of cycle-time is influenced by the external switching device or load. eg. contactor, SSR, valve. A setting that is too long for the
process will cause oscillation and a setting that is too short will cause unnecessary wear to an electro-mechanical switching
device.


Maximum power

100

0 to 100, step 1

Maximum % proportional output of SP3. When using proportional control the output of SP3 will not exceed maximum power setting.



Minimum Power

0

0 to 100, step 1

Minimum proportional output of SP3. When proportional control is used the output of SP3 will not reduce below the minimum power setting.


Output Power

Read Only

0 to 100, step 1

Page 23 of 44