0-5V

Models with 0 to 5V input use an internal resistor to spread the signal across the input range 0 to 50 mV using a
divider of 100. Where a transducer provides a smaller output, the input maximum and minimum values can be
similarly calculated.

0-10V

Models with 0 to 10V input use an internal resistor to spread the signal across the input range 0 to 50 mV using a
divider of 200. Where a transducer provides a smaller output, the input maximum and minimum values can be
similarly calculated.


Decide what scale minimum and maximum will be required, and whether the scale needs inverting.

Example
The example below gives an example of how a 4–20mA input could be configured for an application.

The input to the controller is linear where 4mA = 80 units and 20mA = 300 units.

Action

Parameter

Menu

Parameter

Value


Select input sensor type

Input settings

linear


Select unit

Module settings

select from list, if unit not available select Set


Allocate SP1 output

Output settings

Select output 1, 2 or 3


Enter Linear high

Input settings

Enter 50 (represents 20mA i.e. multiplier 2.5)


Enter Linear low

Input settings

Enter 10 (represents 4mA i.e multipler 2.5)


Enter Linear low scale

Input settings

Enter 80 (i.e. units at 4mA)


Enter Linear high scale

Input settings

Enter 300 (i.e. units at 20mA)


Enter display resolution

Input settings

Set as 0.01, 0.1, 1

Note: changing the display resolution will affect set-point value and other operating parameters. Ensure that
display resolution settings are selected before adjusting set-point and tuning the controller to the application.


ERROR MESSAGES
CALogix-sw error messages are shown below

Tune Fail -

Will be displayed if an autotune cycle fails

1.

Check setpoint is not set at 0

2.

The characteristics of the load exceed the algorithm limits

i. Change conditions e.g. raise setpoint

ii. Try tune at setpoint, atsp

iii. If error persists call local CAL representative.


Input Fail –

Sensor is open/short circuit or linear input is over range. Check sensor/wiring/connections.


Error On/Off – Error On/Off

will be displayed if autotune when in On/Off control.



PID

MODULE

SETTINGS

(*

=

module

position

number)

Module * - settings

Default

Options


Module name

Module *

User defined

A user defined label (name) up to 10 characters can be set for each module.


Operating units

None

°C, °F, Bar, PSI, PH, RH, Set, None

Process-value operating units can be defined as °C, °F, Bar, PSI, Ph, RH or Set.

Important note

: If switching from °C to °F or vice versa, ensure that set-point and other temperature-value based parameter

settings are adjusted accordingly to reflect the change made. Failure do so may result in dangerous operation or damage to the system.

Module * – input settings

Default

Options


Sensor Type

J

B, E, J, K, L, N, R, S, T, RTD 2-wire, RTD 3-wire, linear,
custom sensor**, custom sensor with cjc**.

**consult factory

Display Resolution

1

0.01, 0.1, 1