0.5

0-1.5, step 0.1



Cycle time

10 secs

0.1 to 9.9, step 0.1

10

to

81,

step

1

SP1 proportional cycle-time -

Determines the cycle rate of the output device for proportional control.

The choice of cycle-time is influenced by the external switching device or load. eg. contactor, SSR, valve. A setting that is too long for the
process will cause oscillation and a setting that is too short will cause unnecessary wear to an electro-mechanical switching
device.

Control offset

0

-9999 to 9999, step 0.01

SP1 offset/manual reset -

* ±50% band. Applicable in proportional and ON/OFF mode with integral disable:

Integral time = OFF

.


Maximum power

100

0 to 100, step 1%

Maximum % proportional output of SP1. When using proportional control the output of SP1 will not exceed maximum power setting.


Minimum power

0

0 to 100, step 1%

Minimum proportional output of SP1. When proportional control is used the output of SP1 will not reduce below the minimum power setting.


Output power

Read Only

0 to 100, Step 1%

The current proportional output of SP1 shown as %.


Manual Power

Off

Off, 0 to 100, step 1%

Manual power overrides PID calculated power output. The proportional output for SP1 will remain constant at the entered value. To return to
PID control set manual power to 0.


Module * – Autotune Settings

Default

Options


Mode

Off

Off,

tune,

atsp

Off

Run current PID or On/Off settings

Tune

Tune controller at 75% of set-point

ATSP

Tune controller at setpoint


Use cycle time

No

No,

Yes

No

Use manually entered cycle time

Yes

Automatically apply autotune calculated cycle time


Band

Read Only

Autotune calculated proportional band


Integral time

Read Only

Autotune calculated Integral time


DAC

Read Only

Autotune calculated derivative approach control


Cycle time

Read Only

Autotune calculated cycle time


CtA, CtB, Ct1, Ct2, Ct3, Ct4, Os1, Os2, Us

Read Only, Autotune data


Module * - Setpoint 2 Control

Default

Options


Operating mode

None

DVHI, DVLO, BAND, FSHI, FSLO, COOL, EOP, None

DVHI

Deviation high, alarm output if process value rises above the main setpoint by the value inserted at setpoint2

DVLO

Deviation low, alarm output if process value falls below the main setpoint by the value inserted at setpoint 2

Band

Band, alarm output if process value rises above or falls below main setpoint by value inserted at setpoint2

FSHI

Full scale high, alarm output if process value rises above the value inserted at setpoint2

FSLO

Full scale low, alarm output if process value falls below the value inserted at setpoint2

Cool

See section on heat-cool

EOP

See event outputs in programmer section


Mode

PARK

P, PI, PID,PD, PARK, On/Off

Primary control type for setpoint 2
P

Proportional

PI

Proportional

Integral

PID

Proportional

Integral

Derivative

PD

Proportional

Derivative

Park

Holds controller operation – disables output

On/Off On/Off

Control

PI, PID and PD can only be selected when operating mode is set as Cool


Subsidiary mode

None

LTCH, HOLD, LTHO, NLIN


Setpoint

2 0

-9999 to 9999 step 0.01