Smartcool, Precision air conditioning, W 2 c0 – Airedale SmartCool 11-233kW User Manual

Page 114: Electrical data- w2c0 continued

Advertising
background image


SmartCool

TM

- D

Precision Air Conditioning

114

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013


Electrical Data- W2C0 Continued

SC19D064-W2C0-0

SC19D070-W2C0-0

SC19D076-W2C0-0

Standard Dry Cooler Match

1 x DR95

1 x DR95

1 x DR95

(EC)

Unit Data - W2C0

Nominal Run Amps

(1)

A

78.9

80.3

88

Maximum Start Amps

A

222.7

217.6

260.5

Recommended Mains Fuse Size

A

100

100

100

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data – Cooling Only - w2C0

Nominal Run Amps

A

53.1

56

67.5

Maximum Start Amps

A

196.9

193.4

240

Recommended Mains Fuse Size

A

63

80

80

Evaporator Fan Motor - Per Fan

Motor Type

EC

EC

EC

Quantity x Motor Size

kW

2 x 2.2

2 x 2.2

2 x 2.2

Full Load Amps

A

3.3

3.3

3.3

Locked Rotor Amps

A

3.3

3.3

3.3

Compressor 1 , Circuit 1

Motor Size

(3)

kW

10.86

12.15

13.73

Nominal Run Amps

A

19.2

20.7

24.5

Locked Rotor Amps

A

163

158

197

Type of Start

Direct On Line

Compressor 2, Circuit 1

Motor Size

(3)

kW

10.86

12.15

13.73

Nominal Run Amps

A

19.2

20.7

24.5

Locked Rotor Amps

A

163

158

197

Type of Start

Direct On Line

Standard Dry Cooler Match - Motor Per Fan

AC

AC

EC

Quantity x Motor Size

kW

4 x 0.88

4 x 0.88

4 x 1.68

Full Load Amps

A

1.65

1.65

2.6

OPTIONAL EXTRAS

Electric Heating

Number of stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating (Total)

kW

31.5

31.5

31.5

Current Per Phase

A

45.5

45.5

45.5

Humidifier

Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.2

16.2

16.2

First upgrade Fan Motor - EC Motor - Per Fan

Quantity x Motor Size

(2)

kW

2 x 3.1

2 x 3.1

2 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Second upgrade Motor - EC Motor - Per Fan

Quantity x Motor Size

(2)

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Dry Cooler Match - EC Motor-Per Fan

Quantity x Motor Size

kW

4 x 1.68

4 x 1.68

N/A

Full Load Amps

A

2.6

2.6

N/A

Dry Cooler Match - SCAF Fan

Quantity x Motor Size

kW

4 x 1.94

4 x 1.94

4 x 1.94

Full Load Amps

A

3.4

3.4

3.4

(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed

(3) Values are per compressor

W

2

C0