Commissioning procedure

Refrigeration circuit

Expansion Valve

Record on the commissioning sheet the type of expansion valve fitted to the unit. i.e.

·

Electronic Expansion Valve (EEV)

·

Thermostatic expansion Valve (TEV)

Pressure Switch Settings

Record the design pressure switch settings.

·

High pressure Out

·

Low pressure In

·

Low pressure differential

System Pressure Readings Record on the actual system operating pressures.(Barg)

·

Suction pressure

·

Discharge pressure

·

Liquid pressure

Superheat / Sub cooling

Record the superheat and sub cooling readings, typically 6°C superheat and 3°C Sub-
cooling.

Superheat protects the compressor from liquid flood back and the amount of sub cooling
ensures enough liquid refrigerant to enter the expansion device.

Long pipe runs may require additional sub cooling to overcome the pressure drop of
these lines. This could cause the unit to operate at a reduced capacity.

Compressor currents

Record on the commissioning sheet the operating currents of the compressor. The
current reading is to be taken when the unit is running at full load.

Sight Glass



Check the condition of the sight glass. References on the commissioning sheet are

·

Wet or Dry

·

Clear or Bubbles

The sight glass is used to indicate

·

the condition of the refrigerant in the system

·

lack of sub-cooling

·

refrigerant deficiency

·

Moisture content of the refrigerant.


The colour of the sight glass depends on the moisture content of the refrigerant. The
recommended moisture levels of a system should be between 30 and 75ppm.
An indication of green/dry are to be considered as perfect conditions meaning full
protection by the filter drier against effects from moisture.

If the green colour starts to fade, the colour change from green to yellow has begun and
the indicator should therefore be watched carefully. If the colour changes to yellow it is a
clear signal that the capacity of the filer drier is exceeded and should be replaced as soon
as possible.

CAUTION

Be aware that Polyolester (POE) oil for HFC refrigerants (R134a, R404A, R407C and
R410A) reacts with moisture in a hydrolysis generating acid. Polyolvinyl ether (PVE) oil
does not have the same problem with acid but still requires good refrigeration practice.

Filter Drier

The filter drier ensures that any moisture / debris are captured. The drier should be
installed last in any system prior to evacuation. It should be installed as close to the
expansion valve as possible. If the drier is allowed to be in contact with moisture it can be
difficult to evacuate the system; making the installation time longer.
Airedale recommends that a quality filter drier is used to ensure that the performance of
the system is not reduced.