Performance Data – Dry Coolers

Standard Dry Cooler Fan

Water Entering / Leaving

Ambient

Temperature °C

25°C

30°C

35°C

40°C

45°C

Output

(kW)

Output

(kW)

Output

(kW)

Output

(kW)

Output

(kW)

DR10

35°C/30°C

11

-

-

-

-

40°C/35°C

19.6

11

-

-

-

45°C/40°C

28.1

19.6

11.1

-

-

50°C/45°C

36.6

28

19.6

11.1

-

55°C/50°C

45

36.4

27.9

19.5

11.1

DR12

35°C/30°C

13.6

-

-

-

-

40°C/35°C

24.5

13.7

-

-

-

45°C/40°C

35.2

24.5

13.7

-

-

50°C/45°C

45.9

35.1

24.5

13.8

-

55°C/50°C

56.6

45.7

35.05

4.4

13.8

DR15

35°C/30°C

15..4

-

-

-

-

40°C/35°C

25.6

15.3

-

-

-

45°C/40°C

35.6

25.4

15.3

-

-

50°C/45°C

45.4

35.2

25.2

15.2

-

55°C/50°C

55.2

44.9

34.9

25

15.1

DR20

35°C/30°C

18.3

-

-

-

-

40°C/35°C

31.9

18.3

-

-

-

45°C/40°C

45.1

31.7

18.3

-

-

50°C/45°C

58.1

44.8

31.6

18.3

-

55°C/50°C

71.5

57.7

44.4

31.4

18.3

DR25

35°C/30°C

24.4

-

-

-

-

40°C/35°C

43.1

24.5

-

-

-

45°C/40°C

61.5

43

24.5

-

-

50°C/45°C

79.7

61.2

42.9

24.5

-

55°C/50°C

98

79.3

60.9

42.8

24.6

DR30

35°C/30°C

30.6

-

-

-

-

40°C/35°C

54.5

30.7

-

-

-

45°C/40°C

78

54.5

30.8

-

-

50°C/45°C

101.4

77.8

54.4

30.9

-

55°C/50°C

124.9

101

77.5

54.3

30.9

DR35

35°C/30°C

34.8

-

-

-

-

40°C/35°C

57.4

34.6

-

-

-

45°C/40°C

79.5

56.9

34.3

-

-

50°C/45°C

101.4

78.7

56.4

34.1

-

55°C/50°C

123.3

100.4

77.9

55.9

33.9

DR40

35°C/30°C

42

-

-

-

-

40°C/35°C

72

41.9

-

-

-

45°C/40°C

101.5

71.7

41.8

-

-

50°C/45°C

130.8

101

71.4

41.8

-

55°C/50°C

160.2

130

100.3

71

41.6

DR45

35°C/30°C

44.6

-

-

-

-

40°C/35°C

74.4

44.4

-

-

-

45°C/40°C

103.4

73.8

44.2

-

-

50°C/45°C

132.3

102.5

73.2

43.9

-

55°C/50°C

161.2

131.1

101.6

72.6

43.6

DR50

35°C/30°C

53.1

-

-

-

-

40°C/35°C

91.7

53.1

-

-

-

45°C/40°C

129.7

91.4

53.

-

-

50°C/45°C

167.6

129.2

91.1

53

-

55°C/50°C

205.5

166.8

128.6

90.8

52.9

(1) Output kW refers to the dry cooler heat rejection