Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

25

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Installation Data

Refrigerant Handling

Only certified personnel must charge the systems with refrigerant

CAUTION

Personal protective equipment must be worn when handling refrigerants.

Charging Gauges

The refrigerant Schrader connections on the SmartCool units are 5/16” to allow for the
increase working pressures of R410A. Gauges designed for R410A must only be used.

Refrigerant Quality

The system must be charged with clean virgin refrigerant R410A only.

Refrigerant Charge
Weights

The exact refrigerant charge is dependant on site circumstances and operating
temperatures. Pipework runs must be taken into consideration. The refrigerant charge
must be weighed into the system and recorded within your F-Gas record.

RECORD

Record on commissioning sheet provided once completed.

IMPORTANT

It is important that solenoid valves are energised correctly to ensure that the Hot Gas
ReHeat coil is broken of vacuum (the Normally Closed (NC) valve should be energised).

The use of a magnetic coil lifter is recommended.

The valve must also be energised when charging the system with refrigerant.

The solenoid valve head must be put back on the body before unit operation.

Schrader Caps

Schrader caps must be replaced following connection of service gauges to the unit.

Final Leak Test

A final leak test must be carried out following removal of service gauges prior to leaving
site ensuring that the system complies with F-Gas regulations.