Precision air conditioning, Smartcool, Refrigerant charging guide – Airedale SmartCool 11-233kW User Manual

Page 19

Advertising
background image



Precision Air Conditioning


SmartCool

TM

– D

Precision Air Conditioning

19

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Liquid Line

If the system is configured with the SmartCool higher than the condenser unit h it may
be required to increase the degree of sub cooling to prevent flashing gas. This flashing is
caused by excess pressure drop caused by the static head of refrigerant and can cause
poor operation of the evaporator and metering device.

Careful pipe sizing is recommended to ensure that the liquid does not form gas due to
excess pressure drop

Increasing the liquid line size minimizes pipe friction and flashing due to friction pressure
drop.

However as a fail safe it is recommended that the condenser is installed below the
indoor unit to allow for correct liquid drain.

Pipe Insulation

The liquid line of the system must be insulated if passing through extremely warm places
(Boiler houses etc). Ensuring that the refrigerant does not become flash gas.

Condenser above Air Handling Unit

Condenser below Air Handling Unit

t

4m

t

Discharge Line

Liquid

Diagrams above for illustration only

Refrigerant Charging Guide

The following information can be used to estimate the refrigerant quantity required in a
typical split system installation.

Unit Refrigerant Charge
(kg/Circuit)

The following table shows the refrigerant charge / circuit for the indoor and outdoor units.

Indoor Unit

Standard Condenser

Larger Condenser

(Indoor Unit)

kg/Circuit

HGRH

(1)

kg/Circuit

(Outdoor Unit)

kg/Circuit

(Outdoor Unit)

kg/Circuit

SC19D055-X2X2

4.41

4.56

CR50

4.9

CR65

9.78

SC19D070-X2X2

4.66

4.81

CR65

9.78

CR80

8.37

SC19D080-X2X2

4.66

4.81

CR65

9.78

CR80

8.37

SC25D080-X2X2

5.84

6.04

CR65

9.78

CR80

8.37

SC25D090-X2X2

6.37

6.60

CR65

9.78

CR80

8.37

SC25D100-X2X2

6.38

6.60

CR80

8.37

CR105

16.72

SC31D100-X2X2

7.56

7.83

CR80

8.37

CR105

16.72

SC31D120-X2X2

7.57

7.83

CR105

16.72

CR130

22.05

SC31D130-X2X2

7.67

7.94

CR105

16.72

CR130

22.05

SC19D033-X2C0

4.34

4.49

CR50

4.9

CR65

9.78

SC19D038-X2C0

4.59

4.74

CR65

9.78

CR80

8.37

SC19D045-X2C0

4.59

4.74

CR65

9.78

CR80

8.37

SC19D064-X2C0

5.13

5.33

CR105

16.72

CR130

22.05

SC19D070-X2C0

5.13

5.34

CR105

16.72

CR130

22.05

SC19D076-X2C0

5.14

5.34

CR105

16.72

CR130

22.05

SC25D045-X2C0

5.77

5.97

CR65

9.78

CR80

8.37

SC25D050-X2C0

6.31

6.53

CR65

8.37

CR80

8.37

SC25D055-X2C0

6.31

6.53

CR80

8.37

CR105

16.72

SC25D067-X2C0

6.31

6.56

CR105

16.72

CR130

22.05

SC25D073-X2C0

6.32

6.57

CR105

16.72

CR130

22.05

SC25D080-X2C0

6.32

6.57

CR105

16.72

CR130

22.05

SC31D055-X2C0

7.49

7.75

CR80

8.37

CR105

16.72

SC31D065-X2C0

7.49

7.76

CR105

16.72

CR130

22.05

SC31D075-X2C0

7.49

7.76

CR105

16.72

CR130

22.05

SC31D077-X2C0

7.50

7.79

CR105

16.72

CR130

22.05

SC31D080-X2C0

7.50

7.79

CR105

16.72

CR130

22.05

SC31D083-X2C0

7.50

7.79

CR105

16.72

CR130

22.05

(1)Fitted with optional hot gas re-heat

In

s

ta

ll

a

tion

Warning: May have flash gas occurring
in liquid line if riser friction losses are
excessive.