Smartcool, Precision air conditioning, W 2 w2 – Airedale SmartCool 11-233kW User Manual

Page 96: Mechanical data – w2w2 continued

Advertising
background image


SmartCool

TM

- D

Precision Air Conditioning

96

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Mechanical Data – W2W2 Continued

SC25D080-W2W2

SC25D090-W2W2

SC25D0100-W2W2

Standard Dry Cooler Match

2 x DR55

2 x DR70

2 x DR70

Capacity

Nom Cooling (Gross) – W2

(1)

kW

77.6

84.6

96.3

Total Heat of Rejection – W2

kW

99.2

109.1

124.5

Capacity Steps

4

4

6

Fan Gain

(5)

kW

2.16

2.61

3.01

Dimensions – W x D x H

Mm

2549 x 890 x 1980

2549 x 890 x 1980

2549 x 890 x 1980

Weight – Machine / Operating

(2)

Kg

1090 / 1110

1220 / 1230

1230 / 1250

Construction

Panels: Galvanised Sheet Steel, Epoxy Baked Powder Paint – Black Grey (RAL 7021)

Material/Colour

Frame: Anodised Aluminium Frame with Black Nylon Corners

Evaporator

Rifled Copper Tube/Turbulated Hydrophilic Coated Aluminium Fins

Cooling/Dehum Stages

4/1

4/1

6/1

Condenser

Stainless Steel Brazed Plate

Water Volume

l

11

16.7

16.7

Water Flow

l/s

2.43

2.69

3.09

Pressure Drop Condenser

kPa

47.45

21.32

27.78

Dry Cooler

Water Volume

L

43.2

55.9

55.9

Flowrate

l/s

2.43

2.69

3.09

Pressure drop

kPa

29.8

42

50

Fan Motor

Backwards Curved, Centrifugal direct drive

Motor Type

AC

AC

AC

Quantity x Motor Size

kW

3 x 2.38

3 x 2.38

3 x 2.38

Speed @25Pa / Maximum ESP

RPM

1066 / 1364

1207 / 1360

1360 / 1360

Maximum ESP

Pa

353

203

20

Nominal Airflow

m³/s

5.2

5.9

6.5

Compressor – Scroll

Configuration – W2W2

Dual Circuit – Circuit 1 Tandem Compressors (Water Cooled)

Circuit 2 Tandem Compressors (Water Cooled)

Quantity – W2W2

4

2

2

Oil Charge Volume – W2W2

l

4 x 1.57

4 x 3

4 x 3

Oil Type

Polyolvinyl

Polyolester

Refrigeration

Dual Circuit

Refrigerant control and type

Thermostatic Expansion Valve (Optional EEV)

Refrigerant type

R410A

Holding Charge

Inert Gas

Charge (Per Circuit

kg

8.51

10.85

10.85

Connections

Water Inlet / Outlet –W2

mm

42

42

42

Condensate Drain Hose

mm

22

22

22

Filtration

Disposable to BS EN 779-G4

Quantity

4

4

4

OPTIONAL EXTRAS

Hot Gas Reheat -

(3)

Nom Heating (Gross)

kW

11.5

12.2

12.2

Electric Heating (Total)

kW

21

21

31.5

Humidifier

Capacity

kg/hr

15

15

15

Feed/Drain

3/4" BSPF Braided flexible hose / 19mm hose connection

Condensate Pump

Head

m

10.8

10.8

10.8

Flow

l/m

5

5

5

Drain

10mm Stainless steel Stub Connection

First upgrade Motor - EC Motor

Backwards Curved, Centrifugal direct drive

Quantity x Motor Size

kW

3 x 2.2

3 x 2.2

3 x 2.2

Speed @ 25Pa / Maximum ESP

rpm

1050 / 1360

1187/ 1360

1337 / 1360

Maximum ESP

Pa

337

202

45

Fan Gain

(5)

kW

1.32

1.86

2.6

Second upgrade Motor - EC Motor

Backwards Curved, Centrifugal direct drive

Quantity x Motor Size

kW

3 x 3.1

3 x 3.1

3 x 3.1

Speed @ 25Pa / Maximum ESP

rpm

1069 / 1510

1212 / 1510

1354 / 1510

Maximum ESP

Pa

487

351

195

Fan Gain

(5)

kW

1.3

1.85

2.6

Low Pressure Hot Water

(4)

Copper Tube/Aluminium Fin

Capacity Gross

kW

32.5

34.1

35.7

Water Flow (Nominal)

l/s

0.72

0.76

0.79

Pressure drop

kPa

37.4

21

21.8

LPHW Connection Sizes

mm

22

22

22

(1) Entering air 24°C/45% RH condensing water in / out: 35/40°C
(2) Machine weight Includes a refrigerant charge / Operating weight includes calculated water volume
(3) Based on air temperature of 15.5 °C

leaving the evaporator coil

(4) Based upon low pressure hot water 82 °C inlet / 71°C outlet. Air on 20°C.
(5) Fan gain based on 25 Pa ESP @ nominal air volume. Fan gain figure will change as airflow and ESP change.

W

2

W2

Advertising