118

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013


Electrical Data- W2C0 Continued

SC31D077-W2C0-0

SC31D080-W2C0-0

SC31D083-W2C0-0

Standard Dry Cooler Match

1 x DR95

1 x DR95

(EC)

1 x DR95

(EC)

Unit Data Full Function-W2C0

Nominal Run Amps

(1)

A

88.1

91.9

95.8

Maximum Start Amps

A

225.5

260.2

268.3

Recommended Mains Fuse Size

A

100

125

125

Max Mains Incoming Cable Size

mm²

35

70

70

Mains Supply

V

400V / 3PH + N / 50Hz

Control circuit

VAC

24

24

24

Unit Data Cooling Only - W2C0

Nominal Run Amps

63.8

71.5

75.3

Maximum Start Amps

201.2

244.0

247.8

Recommended Mains Fuse Size

80

80

100

Evaporator Fan Motor - Per Fan

Motor Type

EC

EC

EC

Quantity x Motor Size

(2)

kW

3 x 3.1

3 x 3.1

3 x 3.1

Full Load Amps

A

4.8

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

4.8

Compressor 1 , Circuit 1

Motor Size

kW

12.15

12.15

13.73

Nominal Run Amps

A

20.7

20.7

24.5

Locked Rotor Amps

A

158

158

197

Type of Start

Direct On Line

Compressor 2, Circuit 1

Motor Size

(3)

kW

12.15

13.73

13.73

Nominal Run Amps

A

20.7

24.5

24.5

Locked Rotor Amps

A

158

197

197

Type of Start

Direct On Line

Standard Dry Cooler Match - Motor Per Fan

AC

EC

EC

Quantity x Motor Size

kW

4 x 0.88

4 x 1.68

4 x 1.68

Full Load Amps

A

1.65

2.6

2.6

OPTIONAL EXTRAS

Electric Heating

Number of stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating (Total)

kW

31.5

31.5

31.5

Current Per Phase

A

45.47

45.47

45.47

Humidifier

Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.2

16.2

16.2

First upgrade Fan Motor - EC Motor - Per Fan

Quantity x Motor Size

(2)

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Second upgrade Motor - EC Motor - Per Fan

Quantity x Motor Size

(2)

kW

N/A

N/A

N/A

Full Load Amps

A

N/A

N/A

N/A

Locked Rotor Amps

A

N/A

N/A

N/A

Standard Dry Cooler Match - EC Motor-Per Fan

Quantity x Motor Size

(2)

kW

4 x 1.68

N/A

N/A

Full Load Amps

A

2.6

N/A

N/A

Dry Cooler Match - SCAF Fan

Quantity x Motor Size

(2)

kW

4 x 1.94

4 x 1.94

4 x 1.94

Full Load Amps

A

3.4

3.4

3.4

(1) Values given for function units with standard selections for heating, humidification, supply air fans and matched condenser
at 7°C evaporating and 54.4°C condensing
(2) Stated motor power is based on maximum electrical power absorbed

(3) Values are per compressor