Smartcool, Precision air conditioning, Troub les hoo ting – Airedale SmartCool 11-233kW User Manual

Page 184

Advertising
background image


SmartCool

TM

- D

Precision Air Conditioning

184

Precision Air Conditioning

Installation, Maintenance and Commissioning Manual :6877419 02/2013

Code

Description

A

ut

o

R

es

et

Un

it

D

is

ab

led

Co

m

ponen

t

D

is

ab

led

Cause

Action

AL021

Phase Failure
Alarm

Ÿ

Ÿ

Ÿ

The power meter / phase

failure relay has detected a

phase rotation / fail loss

Alarm is automatically reset once the phase

failure has cleared.

AL022

Water Flood /
Condensate
Pump Alarm

Ÿ

Indicates that excess Water (or

a leak) has been detected by

the unit.

Alarm is generated

AL023

Fire / Smoke
Alarm

Ÿ

Ÿ

Ÿ

Indicates that Fire or smoke

has been detected

Alarm is generated

AL024

Leak Detector
Alarm

Ÿ

Ÿ

Indicates the unit has detected

a refrigerant leak.

Once the refrigerant level in the air has fallen

below set point the alarm will reset

AL025

Over Heat Cut
Out Alarm

Ÿ

Ÿ

This indicates that the auto /

manual overheat cut-out has

tripped and has switched off all

stages of electric heating

This alarm can be auto reset once temperatures

have returned to a normal operating range. The

manual is by a switch in the unit

AL026

Low Pressure
Alarm Circuit 1

Ÿ

Ÿ

Indicates that the low pressure

safety switch has been tripped

and the controller has switched

off circuit 1

Alarm can be manually reset

AL027

Low Pressure
Alarm Circuit 2

Ÿ

Ÿ

Indicates that the low pressure

safety switch has been tripped

and the controller has switched

off circuit 2

Alarm can be manually reset

AL028

Circuit 1
Compressor 1
Maintenance
Alarm

Ÿ

Indicates that the run hours for

the particular component has

exceeded the limit set for its

maintenance alarm.

Once Maintenance has been performed, the

hors run for the component can be reset, which

will reset the alarm.

AL029

Circuit 1
Compressor 2
Maintenance
Alarm

Ÿ

AL030

Circuit 1 Inverter
Compressor
Maintenance
Alarm

Ÿ

AL031

Circuit 2
Compressor 1
Maintenance
Alarm

Ÿ

AL032

Circuit 2
Compressor 2
Maintenance
Alarm

Ÿ

AL033

Circuit 2 Inverter
Compressor
Maintenance
Alarm

Ÿ

AL034

Supply Fans
Maintenance
Alarm

Ÿ

AL035

High Humidity
Alarm

Ÿ

Indicates that the particular

valve has exceeded the high /

low limit. This alarm is delayed

for 2 minutes on start-up to

prevent nuisance alarms. The

cooling or heat demand is

disabled

Once the return air humidity returns below the

high / low limit the alarm is automatically reset.

AL036

Low Humidity
Alarm

Ÿ

AL037

High Return Air
Temperature

Ÿ

Ÿ

Ÿ

Troub

les
hoo

ting

Advertising