TROUBLESHOOTING GUIDE

Trouble

Remedy

No LCD Display

• Battery Powered Version: Check battery voltage Should be 1 5V DC Replace if low or bad
• Loop Powered Version: Check for current flow in the loop Check polarity of the current loop

connections for proper orientation

No Rate or Total

Displayed

• Check connection from meter pickup to display input terminals
• Check turbine meter rotor for debris Rotor should spin freely
• Check programming of flow monitor
• Check to see that the minimum flow rate is being met for the current meter in use Otherwise,

the flow meter will not accurately send pulses to the flow monitor

Flow Rate Display

Interprets Reading

Constantly

• This is usually an indication of external noise Keep all AC wires separate from DC wires
• Check for large motors close to the meter pickup
• Check for radio antenna in close proximity
• Try disconnecting the pickup from the monitor pig tail This should stop the noise If not, then

try reorientating the meter to a new location

Flow Rate Indicator

Bounces

• This usually indicates a weak signal Replace pickup and/or check all connections
• Examine K factor

Default K factor Values

Meter Size

Default K factor

Lower Limit

Upper Limit

3/8 in

20,000

16,000

24,000

1/2 in

13,000

10,400

15,600

3/4 in

2750

2200

3300

7⁄8 in

2686

2148

3223

1 in

870 0

686 0

1044

1-1/2 in

330 0

264 0

396 0

2 in

52 0

41 6

62 0

3 in

57 0

45 6

68 0

4 in

29 0

23 2

35 0

6 in

7 0

5 6

8 0

8 in

3 0

2 4

4 0

10 in

1 6

1 3

2 0