Explosion proof enclosure, Installation, Explosion proof enclosure 7 – Badger Meter B2800 User Manual

Page 7: Installation 7

Advertising
background image

EXPLOSION PROOF ENCLOSURE

The EIH Instrument enclosure is designed to house instrumentation and control equipment as well as act as a conduit outlet

body in hazardous, abusive and wet locations
The EIH enclosure is approved by Underwriters Laboratories Inc , Canadian Standards Association, Factory Mutual and

CENELEC for use in Class I, Groups B*, C** and D; Class II, Groups E, F and G; and Class II hazardous (classified) locations as

defined by the National Electrical Code and Canadian Electrical Code It is also NEMA/UL/CSA Type 4 and IP66 rated for

watertight applications

*With conduit seals installed within 18 inches of enclosure

**Unsealed conduit lengths must not exceed five feet (152 cm)

INSTALLATION

ELECTRICAL POWER MUST BE TURNED OFF BEFORE AND DURING INSTALLATION AND MAINTENANCE.
1 EIH Instrument enclosures are furnished with 3/4 inch NPT offset through feed cast hubs for conduit entries (Use Cooper

Crouse-Hinds RE21-SA to reduce to 1/2 inch hubs )

2 Secure the enclosure to the conduit system If the enclosure has mounting feet, select a mounting location that will

provide sufficient strength and rigidity to support the enclosure as well as the enclosed device and wiring

SELECT A MOUNTING LOCATION SO THAT THE ENCLOSURE WILL NOT BE SUBJECTED TO IMPACT BY HEAVY OBJECTS.

IMPACTS CAN DAMAGE ENCLOSED DEVICES OR GLASS LENS.
3 Install Cooper Crouse-Hinds EYS sealing fittings required by Section 501-5 and/or 502-5 of the National Electrical Code and

Section 18 of the Canadian Electrical Code or any other applicable local codes and when enclosure is installed in Class I

Group B hazardous locations (For CSA Group C applications, unsealed conduit lengths must not exceed

five feet or 152 cm )

THE HAZARDOUS LOCATION INFORMATION SPECIFYING CLASS AND GROUP LISTING OF EACH INSTRUMENT

ENCLOSURE IS MARKED ON THE NAMEPLATE OF EACH ENCLOSURE.

ALL UNUSED CONDUIT OPENINGS MUST BE PLUGGED. PLUG UNUSED CONDUIT OPENINGS WITH COOPER CROUSE-

HINDS PLG2. PLUGS MUST BE A MINIMUM OF 1⁄8 INCH THICK AND ENGAGE A MINIMUM OF FIVE FULL THREADS.
4 Unthread instrument (and power side) covers and carefully set aside to prevent damage to the cover threads and glass

lens (when glass lens cover is used)

5 Pull wires into enclosure making certain they are long enough to make the required connections and to remove the

instrument or power supply if servicing is required Install instrument and power supply, if applicable, and make all

electrical connections

OTEE:

N

When installing device, be sure to check instrument dimensions to avoid interference with clamping ring on glass

lens and the cover on standard units

6 Test wiring for correctness by checking continuity and also check for unwanted grounds with insulator resistance tester

Make sure test equipment being used will not damage instrument to be housed in the EIH Instrument enclosure

7 Carefully re-thread cover to enclosure housing Tighten cover until cover flange contacts body face

Programming Manual

Page 7