SPECIFICATIONS

Power Supply Options

Battery Powered

One D size, 1 5V alkaline battery

Loop Powered

4-20 mA loop power

Power Consumption

Battery Powered

Less than 1 mA @ 1 5V DC

Loop Powered

25 mA (maximum)

Alphanumeric Rate and Total Display

Eight digit, 0 5 inch high numeric display
Eight character, 0 25 inch high alphanumeric display

Pulsed Output Signal

Type

Outputs one pulse for each increment of the least significant totalizer digit

Max Voltage

30V DC

Pulse Type

Opto-Isolated open collector transistor

Pulse Width ON State

20 mS / maximum pulse rate 20 Hz

Current (ON State)

0 9V drop @ 5 0 mA or 0 7V drop @ 0 1 A

Magnetic Pickup Inputs

Frequency Range

0…3500 Hz

Trigger Sensitivity

30 mV p-p

Over Voltage Protected

±30V DC

Frequency Measurement Accuracy ±0 1%

Temperature Drift

50 ppm / °C maximum

Optional Analog Output (Loop Powered Version)

Type

4…20 mA current loop

Resolution

1:4000

Transient Over Voltages

Category 3, in accordance with IEC664

Pollution Degree

2, in accordance with IEC664

Mounting Classification

NEMA/UL/CSA Type 4 (IP66)

Environmental

Operating Temperature

–22…158° F (–30…70° C)

Humidity

0…90% non-condensing

Certification

CSA Ordinary Locations

To -

C22 2 No 1010-1 for Canada

ISA S82 02 for US

CSA Hazardous Locations

For -

Class I, Div 1 Groups B,C, D

Class II, Div 1 Groups E, F, G

Class III; Type 4X; T6 @ 70° F

To -

C22 2 No 30 for Canada

FM3615 for US

Flow Monitor, B2800XP Explosion Proof Monitor – Simplified

Page 6

November 2013