Turbine Flow Sensor

Installation & Operating Instructions

Page 14

03/12 Form No. 05-TUR-UM-00194

V. OPERATION

General

WARNING

Do not exceed allowable pressure ratings. Pressure in excess of the maximum allowable ratings may

cause the turbine body to fail. Failure to follow these instructions could result in serious personal injury

or death and/or damage to the equipment.

DO - Allow fluids to warm to operating temperatures before critical measurements are taken.

DO - Maintain a flooded condition in the flow sensor at all times. Air and turbulence will result in erroneous

readings.

DON’T - Exceed the working temperature range of –4 °F to +300 °F (–20 °C to +150 °C). Higher

temperatures will damage the magnetic pick-up and lower temperatures will limit the rotation of the

turbine.

Flow Sensors with IFC Option

As soon as power is applied, the IFC will begin to output an analog value representative of the measured

frequency from the turbine meter.

Refer to the wiring diagram that corresponds to the IFC being utilized. See pages 11 and 12.

VI. MAINTENANCE

WARNING

Always disconnect the primary power source before inspection or service. Failure to follow these

instructions could result in serious personal injury or death and/or damage to the equipment.

1. A schedule for maintenance checks should be determined based upon environmental conditions and

frequency of use. Inspect at least once a year.

2. Perform visual, electrical and mechanical checks on all components.

a. Visually check for undue heating evidenced by discoloration of wires or other components,

damaged or worn parts, or excessive corrosion of the device.

b. Electrically check to make sure that all connections are clean and tight and that the device is

operating properly.