Series 3050 Btu Monitor

Analog Input

As an alternative to the pulse inputs, the Series 3050 can accept an Analog input. The input is non-isolated, but can accept

0-1VDC, 0-5VDC, 0-10VDC, 0-20mA and 4-20mA with both factory-defined and custom units of measure.

Low impedance 100 Ohm input for current inputs optimizes performance and flexibility or loop power supplies. Both the

low- and high-end scaling are independent and field configured by the installer.

NOTE: See the Programming Flow Chart on page 18 for required input configuration.

1 ANALOG IN+

2 ANALOG IN-

3 SHIELD

4 SENSOR IN

5 GND

6 SHIELD

7 SENSOR PWR

Figure 5: 4-20mA Analog Loop Powered Wiring

1 ANALOG IN+

2 ANALOG IN-

3 SHIELD

4 SENSOR IN

5 GND

6 SHIELD

7 SENSOR PWR

Figure 6: Voltage or Current Sourcing Analog Inputs