Badger Meter 3050 Series Btu Monitor User Manual

Page 27

Advertising
background image

Page 27

6-11

Installation & Operation Manual

BTU CONFIGURATION

Btu rate units = [0-5] – set the Btu rate units:

0: kBtu/hr

1: Btu/min

2: kW

3: TR

4: J/s

5: Custom

Btu rate ndigits = [2-10] – number of decimal digits to display

Btu rate custom label = [string] – Btu rate custom unit label

Btu rate custom conv = [0-100] – custom unit conversion

factor

Btu total units = [0-6] – Btu totalizer units:

0: BTU

1: kBTU

2: MBTU

3: kWh

4: MWh

5: kJ
6: Custom

Btu total ndigits = [2-10] – number of decimal digits to

display

Btu total custom label = [string] – Btu totalizer custom

unit label

Btu total custom conv = [0-100] – custom unit

conversion factor

Btu total mode = [0-2] – totalizer mode:

0: Heating

1: Cooling

2: Heating & Cooling

Btu sensor type = [0-4] – temperature sensor type:

0: DI Thermistor

1: DI RTD

2: Custom Thermistor

3: Custom RTD

4: No sensor

Btu sensor correct_k = [0-10] – correction factor

Btu sensor temp_unit = [0-1] – temperature units to

display

0: deg F

1: deg C
Btu sensor t2adj = [-10-10] – t2a

RELAY OUTPUT CONFIGURATION

relay [1-5] func = [0-9] – relay function; relay 5 is the pulse

output

0: Totalizer

1: Alarm

2: Manual Control

relay [1-5] input = [0-8] – relay input; depends on source

for totalizer:

0: Flow 1 Total

for alarms:

0: Flow 1 Rate

relay [1-5] units = [0-19] – units on setpoints/rates; depends on

src/input

flow units: same as 'flow [1-2] rate units' above

volume units: same as 'flow [1-2] total units'

relay [1-5] manual = [on/off] – manually set relay on or off, if in

manual mode

relay [1-5] rate = [x] – totalizer rate

relay [1-5] ctime = [0-10000] – pulse width in milliseconds

relay [1-4] latch = [on/off] – turn on/off relay latching

relay [1-4] setpoint = [x]

relay [1-4] releasepoint = [x]

ANALOG OUTPUT CONFIGURATION

analogout [1-2] func = [0-3]

0: Flow rate

1: BTU rate

2: Temperature

3: PID control

analogout [1-2] src = [0-4]

for flow rate:

0: Flow 1 rate

1: Flow 2 rate

2: Flow sum

3: Flow 1-2

4: Flow 2-1

for Btu rate: not used

for temperature:

0: Flow rate

1: Temp 2

2: Temp Delta

for PID control:

0: Flow 1 rate

1: Flow 2 rate

analogout [1-2] range – [0-1]

0: 0-20mA

1: 4-20mA

analogout [1-2] low = [x] – value corresponding to 0 (or 4) mA

analogout [1-2] high = [x] – value corresponding to 20mA

analogout [1-2] setpoint = [x] – PID setpoint

analogout [1-2] P = [x] – PID constants

analogout [1-2] I = [x] – PID constants

analogout [1-2] D = [x] – PID constants