Badger Meter 3050 Series Btu Monitor User Manual

Page 9

Advertising
background image

Page 9

6-11

Installation & Operation Manual

Flow Sensor Wiring

The Series 3050 flow sensor inputs are extremely versatile, designed to accept either two-wire or three-wire pulse inputs

(Data Industrial 200 Series, SDI or 4000 Series) or Analog inputs. Although different rear panel terminals are used, all

parameters are set with the LCD/keypad interface. There are no internal or external jumpers, switches or potentiometers to

move or adjust.

The following pulse input types are accommodated.

Pulse-DI: Used for all Badger Meter Data Industrial Flow Sensors. Provides an internal pull-up resistor and uses “K”

and “Offset” values for calibration.

Pulse–K Factor: Accepts non zero-crossing inputs but provides no internal pull-up, classical “K” ( pulses/gallon)

values for calibration.

Pull-up-K Factor: Provides an internal pull-up resistor and uses classical “K” ( pulses/gallon) values for calibration.

NOTE: All the above pulse input types wire the same as shown in Figure 4. See the Programming Flow Chart on

page 18 for required input configuration.

1 ANALOG IN+

2 ANALOG IN-

3 SHIELD

4 SENSOR IN

5 GND

6 SHIELD

7 SENSOR PWR

Figure 4: Data Industrial Flow Sensor Wiring Examples (Two- and Three-Wire Pulse Types)

Advertising