Temperature Input

The Series 3050 Btu Monitor can accept inputs from either a pair of thermistors or RTDs. The inputs are labeled T1 and T2.

Since the T1 sensor is used to convert the volumetric flow (Example: GPM) to the mass flow ( Example: Lbs/Hr) used in the Btu

calculations, the sensor connected to T1 should be in the same supply or return line as the Flow Sensor.

The temperature inputs of the Series 3050 are extremely versatile. In addition to the factory default two-wire10k @77°F Type

II Thermistors and three-wire 100 ohm Platinum RTDs, the unit can be programmed in the field for a wide variety of custom

RTDs and thermistors. Refer to the Programming Flow Chart. Contact the factory for assistance with any custom inputs.

Wiring Two Wire Thermistors and RTD’s

Wiring Three Wire RTD’s

1 TEMP 1 IN +

2 TEMP 1 IN -

3 TEMP 1 GND

4 SHIELD

5 TEMP 2 GND

6 TEMP 2 IN -

7 TEMP 2 IN +

Jumpers

2 Wire

Thermistor

Located

in same

Supply

or

Return line

Flow Sensor

2 Wire

Thermistor

3 Wire

RTD

T1

Located

in same

Supply

or

Return line

as

Flow Sensor

3 Wire

RTD

Same Colored 2 Wires

Different Color Wire

Different Wire

1 TEMP 1 IN +

2 TEMP 1 IN -

3 TEMP 1 GND

4 SHIELD

5 TEMP 2 GND

6 TEMP 2 IN -

7 TEMP 2 IN +

Figure 7: Wiring Two-Wire Thermistors and RTDs

Wiring Two Wire Thermistors and RTD’s

Wiring Three Wire RTD’s

1 TEMP 1 IN +

2 TEMP 1 IN -

3 TEMP 1 GND

4 SHIELD

5 TEMP 2 GND

6 TEMP 2 IN -

7 TEMP 2 IN +

Jumpers

2 Wire

Thermistor

Located

in same

Supply

or

Return line

Flow Sensor

2 Wire

Thermistor

3 Wire

RTD

T1

Located

in same

Supply

or

Return line

as

Flow Sensor

3 Wire

RTD

Same Colored 2 Wires

Different Color Wire

Different Wire

1 TEMP 1 IN +

2 TEMP 1 IN -

3 TEMP 1 GND

4 SHIELD

5 TEMP 2 GND

6 TEMP 2 IN -

7 TEMP 2 IN +

Figure 8: Wiring Three-Wire RTDs