Badger Meter 3050 Series Btu Monitor User Manual

Page 12

Advertising
background image

Page 12

6-11

Series 3050 Btu Monitor

Solid State Switch and Form “C” Output Wiring

The Series 3050 Btu Monitor has one Normally Open (N.O.) solid state switch, and one solid state form “C” relay.

Check the Specifications on page 29 for maximum voltage and current ratings for each type output. These outputs are

completely independent, electrically isolated, and can be programmed as either Pulse or Set Point outputs.

When the “Totalizer” function is selected, the unit of measure and resolution are independent from the displayed units and

can be programmed where one pulse occurs once every 0000000.1 to 999999999. of units selected, with any pulse width

from 0001 to 9999mS.

When the “Alarm” is selected as the unit of measure and the resolution is independent from the displayed units, it allows the

unit to be programmed as either a high or low rate Set Point. Since the Set Point, Release Point and their associated time

delays are fully independent, this output can be either a classical high rate or low rate alarm, depending on the settings

selected. When design planning, keep in mind that although both of these outputs can be programmed as alarm points only,

the relay provides both N.O. and N.C. contacts. The switch is a simple N.O. contact.

Examples:

High Flow Set Point Control

The Set Point must be a value greater than the Release Point.

The relay output will have continuity between its N.C. terminal and “COM” until the flow has exceeded the Set Point (“SETPT”)

for a continuous period of time exceeding the Set Point Delay (“SDLY”), at which time the N.C. connection will open and the

N.O. contact will have continuity to the “COM” terminal. When the flow has dropped below the Release Point (“RELP") for a

continuous period of time exceeding the Release Point Delay (“RDLY”), the relay states will return to their original states. If the

latch has been set to “ON”, the relay will not release until manually reset once the Set Point and Set Delay have been satisfied.

Sources for the Set Point control can be Flow Rate, Energy Rate, T1, T2 or Delta T.

Low Flow Set Point Control

The Set Point must be a value less than the Release Point.

The relay output will have continuity between its N.C. terminal and “COM” until the flow drops below the Set Point (“SETPT”)

for a continuous period of time exceeding the Set Point Delay(“SDLY”), at which time the N.C. connection will open and the

N.O. contact will have continuity to the “COM” terminal. When the flow has again risen above the Release Point (“RELP”) for a

continuous period of time exceeding the Release Point Delay (“RDLY”), the relay states will return to their original states. If the

latch has been set to “ON”, the relay will not release until manually reset once the Set Point and Set Delay have been satisfied.

Sources for the Set Point control can be Flow Rate, Energy Rate, T1, T2 or Delta T.

1 RELAY 1 NO

2 RELAY 1 NC

3 RELAY 1 COM

4 PULSE 1 OUT

5 PULSE 2 OUT

Figure 9: Relay and Switch Wiring Examples

Advertising