Badger Meter 3050 Series Btu Monitor User Manual

Page 28

Advertising
background image

Page 28

6-11

Series 3050 Btu Monitor

RS485 COMM PORT CONFIGURATION

comm baudrate = [0-7]

0: Auto

1: 300

2: 1200

3: 2400

4: 9600

5: 19200

6: 38400

7: 76800

comm mstpaddr = [0-127] – BACnet/MSTP address

comm maxmaster = [0-127] – BACnet/MSTP max master

address

comm devinst = [x] – BACnet device instance ID

comm mbslaveaddr = [0-255] – Modbus slave address

MODBUS

Addr Function

1 Flow 1 rate (GPM)

2 Flow 2 rate

3 Flow 1 Total (gallons)

4 Flow 2 Total

5 BTU Rate (kBTU/hr)

6 BTU Total (kBTU)

7 Batch 1 Count

8 Batch 2 Count

9 Temp 1 (deg F)

10 Temp 2

11 Temp Delta (T2-T1)

TROUBLESHOOTING

Trouble Codes:

1 Relay 1 totalizer rate exceeded

2 Relay 2 rate exceeded

3 Relay 3 rate exceeded

4 Relay 4 rate exceeded

5 Pulse out rate exceeded

20 Error reading EEPROM on faceplate

21 Error writing EEPROM

22 Analog Input card missing

24 Temperature Input card missing

25 Invalid flow units configured

26 Invalid volume units configured

27 Bad input frequency

29 Internal error calculating flow rate

31 Error reading from analog input AD converter

channel 1

32 Error reading from analog input AD converter

channel 2

36 Error writing to analog input AD converter channel 1

37 Error writing to analog input AD converter channel 2

50 Error reading I2C address 0 (relays, buttons, and LEDs)

51 Error writing to I2C address 0

52 Error reading I2C address 1 (analog input card control lines)

53 Error writing I2C address 1

54 Error reading I2C address 2 (temperature input card control lines)

55 Error writing I2C address 2

71 Watchdog timer reset occurred

82 Fatal error initializing EEPROM