Figure 15: 4-20 ma calibration setup, Figure 15: 4-20 ma calibration setup 20, Temperature – Badger Meter Model IOG User Manual

Page 20: Ac+dc

Advertising
background image

P1

Freq. In

4-20mA

Iso Total Pluse

TR_B

TR_A

RS485 Gnd

Setpoint 1

Setpoint 2

Gnd

+

Total Reset

OC Total Pluse

Signal Gnd

TB1

Mag

Pulse

Iso

OC

Low

High

+

+

Input

Total P

ulse

Sig
nal

JP1

JP2

JP3

4-20 mA

Current Loop

(10…28V DC)

POWER

SUPPLY

10A MAX

FUSED

400mA

FUSED

CAT III

1000V

HOLD

MIN MAX

REL

Hz % ms

RANGE

AutoHOLD FAST MIN MX

LOGGING

YES

CANCEL

SAVE

NO

SETUP

µA

mA

A

W

V

TEMPERATURE

COM

OFF

nS

W

VIEW MEM

CLEAR MEM

V

dB

mV

dB

ac+dc

V

ac+dc

A

mA

mV

ac+dc

mA

A

µA

ac+dc

µA

°C

°F

MEM

HM

MS

51000

AUTO MANUAL

%

FA S T M A X M I N AV G

0

0

LOG

HOLD

Figure 15: 4-20 mA calibration setup

20 mA ADJUSTMENT (20mAOut)

The 20 mA adjustment is performed using the same procedure as the 4 mA adjustment While monitoring the ammeter,

adjust the 20 mA DAC value to obtain a 20 mA reading The

arrow button increases the DAC value and the ►

arrow button

decreases the DAC value. When a steady 20 mA reading is obtained on the ammeter, press the ENTER

button to lock in this value and move to the next parameter

4-20 mA TEST (4-20Tst)

The ER-500 monitor contains a diagnostic routine that allows the simulation of mA output values between 4 and 20 to

check output tracking At the 4-20 Tst prompt the current is shown as a flashing number Use the

arrow button to

increase the simulated mA output in increments of 1 mA The

arrow button decreases the mA output. The ammeter

should track the simulated mA output If a 4-20 mA test is not necessary, press the ENTER button once to move to the

next parameter

NOTE:

N

Pressing the ENTER button when the monitor is in test mode causes the monitor to exit the test mode and move on

to the next programming parameter

Linearization (Linear)

Extended Function

Enhanced accuracy is obtained by linearization of the display The linearization function accepts a maximum of ten

points Linearization requires additional calibration data from the meter to be used with the monitor Typically, calibration

information can be obtained in three, five, and ten points from the flow meter’s manufacturer If linearization is not

needed, press the

arrow button to advance to the next parameter The maximum number of linearization

points is 10

Number of Points (Lin Pts)

At the Linear prompt, press the ENTER button once The linear points Lin Pts value is displayed If the number of points

is set to 0, linearization is disabled Press the ENTER button and the most significant digit of the number of points entry

begins to flash The first number can either be a 1 or a 0 only Use the

arrow button to change the first digit Press the

arrow button once to move to the least significant digit

NOTE:

N

If a number other than 0 or 1 is entered in this field the display flashes "Limit" indicating that an over range value has

been entered when the ENTER button is pressed

Again, the

arrow button increments the value When the number of points has been input, press the ENTER button

once to move to the first linear points frequency entry

ER-500 Flow Monitor

Page 20

August 2013