Figure 20: hardware reset, Figure 20: hardware reset 26, Normally open pushbutton switch – Badger Meter Model IOG User Manual

Page 26

Advertising
background image

Clear Grand Total (Clr G-T)

Basic Function

At the clear grand total Clr G-T prompt, press the ENTER button once The display now says no on the screen To clear the

grand total press either the

arrow or the ► arrow button to change from No to Yes Press the ENTER button to select Yes

and advance to the next parameter The totalizer can also be reset using a hardware reset as shown in

Figure 20

JP1

JP2

JP3

Input

Total P

ulse

Sig
nal

P1

Freq. In

4-20mA

Iso Total Pluse

TR_B

TR_A

RS485 Gnd

Setpoint 1

Setpoint 2

Gnd

+

+

+

Total Reset

OC Total Pluse

Signal Gnd

TB1

Mag

Pulse

Iso

OC

Low

High

Normally Open

Pushbutton

Switch

Figure 20: Hardware reset

Password (Passwd)

Basic Function

Password protection prevents unauthorized users from changing programming information Initially, the password is set to all

zeros If the current setting requires a change, press the ENTER button once at the password Passwd prompt The first digit of

the password begins to flash Use the

arrow button to increment the digit until it matches the first number of the desired

password Use the

arrow button to advance to the next digit of the desired password value then use the ▲ arrow button

to increment the display digit until it matches the next digit of the desired password Repeat this step for the all the digits of

the password and then press the ENTER button once to save the new password and advance to the next parameter

Reset Password (RstPswd)

Basic Function

Reset password parameter prevents unauthorized users from manually resetting the flow monitor’s main totalizer Initially,

the password is set to all zeros To change the reset password, press the ENTER button once at the reset password RstPswd

prompt The first digit of the password begins to flash Use the

arrow button to increment the digit until it matches the first

number of the desired password Use the

arrow button to advance to the next digit of the desired password value then

use the

arrow button to increment the display digit until it matches the next digit of the desired password Repeat this

step for the all the digits of the password and then press the ENTER button once to save the new password and advance to

the next parameter

NOTE:

N

Entering a password in the Passwd screen and leaving the password blank in the RstPswd screen allows for total resets

(not requiring a password), but restricts programming modification

ER-500 Flow Monitor

Page 26

August 2013

Advertising