SPECIFICATIONS

LCD

Simultaneously shows Rate and Total

5 x 7 Dot Matrix LCD, STN Fluid

6 Digit Rate, 0 5 inch (12 7 mm) numeric

7 Digit Total, 0 5 inch (12 7 mm) numeric

Engineering Unit Labels 0 34 inch (8 6 mm)

Annunciators

Alarm 1(

1

), Alarm 2 (

2

), Battery Level (

), RS485 Communications (

COM

)

Power

Battery

3 6V DC D size lithium cell gives up to 6 years of service life

Loop

4-20 mA, two wire, 25 mA limit, reverse polarity protected, 7 V DC loop loss

Auto switching between internal battery and external loop power;

includes isolation between loop power and other I/O

Inputs

Magnetic Pickup

Frequency Range

1…3500 Hz

Frequency Accuracy

±0 1%

Over Voltage

Protection

28V DC

Trigger Sensitivity

30 mV

p-p

(High) or 60 mV

p-p

(Low) - (selected by circuit board jumper)

Amplified Pulse

Direct connection to amplified signal (pre-amp output from sensor)

Outputs
Analog 4-20 mA

4-20 mA, two-wire current loop 25 mA current limit

Totalizing Pulse

One pulse for each Least Significant Digit (LSD) increment of the totalizer

Pulse Type

Opto-isolated (Iso) open collector

transistor

Non-isolated open drain FET

(selected by circuit board jumper)

Maximum Voltage

28V DC

Maximum Current

Capacity

100 mA

Maximum Output

Frequency

16 Hz

Pulse Width

30 mS fixed

Status Alarms

(Advanced Only)

Type

Open collector transistor Adjustable flow rate with programmable dead

band and phase

Maximum Voltage

28V DC

Maximum Current

100 mA

Pull-Up Resistor:

External required (2 2 K Ohm minimum, 10 K Ohm maximum)

Modbus

(Advanced Only)

Modbus RTU over RS485, 127 addressable units / 2-wire network, 9600 baud, long integer and single

precision IEEE754 formats; retrieve: flow rate, job totalizer, grand totalizer, alarm status and battery

level; write: reset job totalizer, reset grand totalizer

Data

Configuration

and Protection

Two 4-digit user selectable passwords; level one password enables Job Total reset only, level two

password enables all configuration and totalizer reset functions (Not Applicable on solar powered

units)

Totalizer Operation

Common

Functions

Monitors contain two totalizers: Job and Grand The user can enable/disable the Grand Totalizer

function If Grand Totalizer is enabled, it shares the 7-digit display line with the Job Totalizer –

dwelling between Job and Grand Grand Totalizer rollovers are displayed with a Count value that

increments at each rollover Totalizers are automatically backed up into non-volatile FLASH memory

every 20 minutes and prior to battery expiration; manually via keypad or when signaled via

Modbus (Advanced Model only)