Safety requirements ce label, Safety – Badger Meter SRD/SRI Valve Positioners User Manual

Page 11

Advertising
background image

1)

Details see Certificates of Conformity. With built-in “Inductive
Limit Switch” Code T only –20 °C

2) Below –20 °C reaction time for value changes is reduced
3) Under service as directed
4) With PROFIBUS or FOUNDATION Fieldbus only, if shield of wiring

is grounded on both sides.

5) With appropriate order only
6) National requirements must be observed

Ambient conditions

Operating conditions . . . . . . acc. to IEC 654-1

The device can be operated at a class Dx location

Ambient temperature for

Operation

1)

. . . . . . . . . . . –40 to 80 °C (–40 to 176 °F)

Transport and storage . . . –40 to 80 °C (–40 to 176 °F)
Storage conditions acc.

to IEC 60721-3-1: . . . . . . 1K5; 1B1; 1C2; 1S3; 1M2

Display

LCD (visible)

2)

. . . . . . . . –25 to 80 °C (–13 to 176 °F)

LEDs . . . . . . . . . . . . . . . –40 to 80 °C (–40 to 176 °F)

Relative humidity . . . . . . . . . up to 100 %
Protection class

acc. to IEC 529. . . . . . . . . IP 66

3)

acc. to NEMA . . . . . . . . . . Type 4X

Electromagnetic compatibility EMC

Operating condititions: . . . . . industrieal environment
Immunity according to
- EN 61 326-1 . . . . . . . . . . . fulfilled
Emission according to
- EN 55 011,

Group 1, Class B . . . . . . . . fulfilled

NAMUR

recommendation NE21. . . . fulfilled

SAFETY REQUIREMENTS

CE label

Electromagnetic
compatibility

4)

. . . . . . . . . . . 2004/108/EG

Low-voltage regulation . . . . . not applicable

Safety

According to EN 61010-1
(or IEC 1010-1) . . . . . . . . . . safety class III

Overvoltage Category I

Internal fuses . . . . . . . . . . . . only with PROFIBUS or

FOUNDATION Fieldbus,

but not replaceable

External fuses . . . . . . . . . . . limitation of power supplies

for fire protection must be observed acc. to

EN 61010-1, appendix F (or IEC 1010-1).

Compliance with the essential health and safety

requirements has been assured by compliance with

EN 50014:1997 + A1 + A2 EN 50018:2000

Electrical Classification

5) 6)

See certificate of conformity EX EVE0109 A (de)(en)

Type of protection ATEX “Ex d – Flameproof”
II 2 G EEx d IIC

Temperature class T4...T6

(Design AD 639)
EC-Type-Examination Certificate

PTB 02 ATEX 1084 X

Permissible ambient temperature range:
Temperature class T4 . . . . . –30 °C to +80 °C

(–22 °F to 176 °F)

Temperature class T4 . . . . . (on request)

–40 °C to +80 °C

(–40 °F to 176 °F)

Temperature class T6 . . . . . –30 °C to +75 °C

(–22 °F to 167 °F)

Temperature class T6 . . . . . (on request)

–40 °C to +75 °C

(–40 °F to 167 °F)

For connections in explosion protected hazardous areas

according to directive 94/9/EG appendix II, with the

following maximum values:
Input circuit:

Maximum electrical power . . . . . . . P max = 2.5 W
Electrical connections . . . . . . . . . . U max = up to 60 V
Self-heating of device surface . . . . 1.3 K/W

Type of protection FM “explosion proof”
Class I Division 1, Groups B, C, D
hazardous locations, indoor and outdoor, NEMA 4X

POS-UM-00012-EN-02